{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-5ED32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-5ED32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-5ED32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-5ED32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class M, Icu=55kA @ 415V, 3-pole, line protection TM210, FTFM, In=80A overload protection Ir=80A fixed, short-circuit protection Ii=10 x In, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1180-5ED32-0AA0-ZD00 is a 3-pole IEC frame 160 molded-case circuit breaker with a 55 kA breaking capacity at 415 V (class M). It is configured for line protection with a TM210 thermal-magnetic trip unit: overload protection set fixed at 80 A (Ir = 80 A) and short-circuit protection at 10× In (Ii = 10 × 80 A = 800 A). A nut keeper kit is included for DC Power OEM applications in China. The fixed 80 A Ir suits dedicated loads (a 75–80 A continuous motor or feeder) where you don't need adjustable overloads. The 10× In short-circuit pickup (Ii) is standard for motor branch circuits, allowing inrush without nuisance tripping. The 3VA1 frame mounts in standard panel or enclosure cutouts; the nut keeper kit simplifies DC-side OEM wiring in Chinese-built power cabinets. No DIN-rail snap-on here — it's a bolted-frame breaker for fixed installation.","metaTitle":"Siemens 3VA1180-5ED32-0AA0-ZD00 Circuit Breaker, 55kA @ 415V","metaDescription":"Siemens 3VA1180-5ED32-0AA0-ZD00 IEC frame 160 circuit breaker, 3-pole, 55kA breaking capacity @ 415V, 80A fixed overload, 10x In short-circuit. Current lifecycle. Quoted on request","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6b64fa70950d0eb5ab2c83d9d5398bb6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667849&mlfb=3VA1180-5ED32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-5ED32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of this circuit breaker?","answer":"It is a 3-pole IEC frame 160 breaker with 55 kA breaking capacity at 415 V, fixed 80 A overload protection (Ir), and 10× In short-circuit protection (Ii)."},{"question":"Where can I buy 3VA1180-5ED32-0AA0-ZD00 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-5ED32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-5ED32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}