{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-5EE42-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-5EE42-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-5EE42-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-5EE42-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160 circuit breaker, breaking capacity class M, 4-pole, In=80A, Icu=55kA @ 415V, TM220 overload, ATFM, Ir=56-80A, Ii=10 x In.","salesMarkdown":"The Siemens 3VA1180-5EE42-0AA0-ZD00 is a 4-pole circuit breaker in the 3VA1 IEC frame 160, rated In=80A with a breaking capacity class M — Icu=55kA at 415 VAC. The TM220 thermal-magnetic trip unit provides overload protection adjustable from Ir=56 A to 80 A, and fixed short-circuit protection at Ii=10 x In (800 A). This variant includes an ATFM (Adjustable Thermal Fixed Magnetic) trip, an unprotected N conductor, and a nut keeper kit, specified for DC Power OEM use in China. The 80 A frame and adjustable overload (56–80 A) let it match motor or feeder loads within that window. Fixed Ii at 10 x In means magnetic pickup at 800 A; verify coordination with downstream devices if selectivity is required.","metaTitle":"Siemens 3VA1180-5EE42-0AA0-ZD00 Circuit Breaker, 80A, 55kA @","metaDescription":"Siemens 3VA1180-5EE42-0AA0-ZD00 circuit breaker, IEC frame 160, breaking capacity class M, Icu=55kA @ 415V, 4-pole, In=80A, overload Ir=56-80A, lifecycle current, available to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a07be315c20a0b531c3344a3a452cea.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667852&mlfb=3VA1180-5EE42-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-5EE42-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1180-5EE42-0AA0-ZD00 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is 3VA1180-5EE42-0AA0-ZD00's listed description?","answer":"The listed description is: circuit breaker 3VA1 IEC frame 160 breaking capacity class M Icu=55kA @ 415V 4-pole, line protection TM220, ATFM, In=80A overload protection Ir=56A...80A short-circuit protection Ii=10 x In N conductor unprotected nut keeper kit for DC Power OEM in China."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-5EE42-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-5EE42-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}