{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-5EF32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-5EF32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-5EF32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-5EF32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, 3-pole, 80A, breaking capacity class M, Icu=55kA @ 415V, TM240, ATAM, overload Ir=56A...80A, short-circuit Ii=5...10 x In, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1180-5EF32-0AA0-ZD00 is a 3-pole IEC frame 160 molded case circuit breaker, rated 80 A continuous and carrying a 55 kA interrupting capacity at 415 V (class M). The overload protection is adjustable via the TM240 thermal-magnetic trip unit: Ir spans 56 A to 80 A, so you dial in the exact continuous current for the downstream load. This is a DIN-rail-mount frame 160 breaker — it clips onto the standard top-hat rail inside the enclosure, no drilling or mounting plate needed. The nut keeper kit (included per the order code suffix) is a small but time-saving detail for the OEM or panel builder: it holds the terminal nuts captive during wiring, so you're not fishing dropped hardware out of a live panel. The breaker's 3-pole form factor takes three module-width slots on the rail; plan your fill factor accordingly.","metaTitle":"Siemens 3VA1180-5EF32-0AA0-ZD00 Circuit Breaker, 80A, 55kA @","metaDescription":"Siemens 3VA1180-5EF32-0AA0-ZD00 IEC frame 160 circuit breaker, 3-pole, 80A, Icu=55kA @ 415V. Overload Ir=56-80A, short-circuit Ii=5-10xIn. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/db962c1deff7de95feb1969d2731e5a4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667853&mlfb=3VA1180-5EF32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-5EF32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1180-5EF32-0AA0-ZD00 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ through the storefront."},{"question":"What is the interrupting rating of this breaker?","answer":"The 3VA1180-5EF32-0AA0-ZD00 has an Icu of 55 kA at 415 V, which is the class M breaking capacity level for the 3VA1 IEC frame."},{"question":"What is the overload and short-circuit adjustment range?","answer":"Overload protection Ir is adjustable from 56 A to 80 A via the TM240 thermal-magnetic trip unit. Short-circuit magnetic pickup Ii is fixed at 5 to 10 times In, or 400–800 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-5EF32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-5EF32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}