{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-5EF32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-5EF32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-5EF32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-5EF32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1180-5EF32-0HA0, molded case circuit breaker, 3-pole, 80 A at 40 °C, TM240 thermal-magnetic release, shunt trip (STL), 187 kA interrupting at 240 V AC.","salesMarkdown":"The 3-pole construction and shunt trip (STL) auxiliary release make it suited for remote emergency-off circuits in control panels. Interrupting rating drops as voltage climbs: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. This is the SCCR the breaker can clear at the line side — coordination studies should use the voltage-specific value, not the highest number. Rated 80 A from 40 °C through 50 °C, then derates to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. The 3-pole footprint matches the standard SENTRON 3VA mounting pattern — it drops into the same panel cutout and bus-bar arrangement as other 3VA frame sizes. No rewiring of the bus stack needed if replacing a same-frame 3VA breaker.","metaTitle":"Siemens 3VA1180-5EF32-0HA0 SENTRON MCCB, 80A, 3-Pole, 187kA","metaDescription":"Siemens 3VA1180-5EF32-0HA0 SENTRON molded case circuit breaker, 80A rated at 40°C, 3-pole, 187kA breaking at 240V. Shunt trip release. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"80 A","at 45 °C":"80 A","at 50 °C":"80 A","at 55 °C":"78 A","at 60 °C":"77 A","at 65 °C":"75 A","at 70 °C":"74 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.2 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11805EF320AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=181664&mlfb=3VA1180-5EF32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-5EF32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of 3VA1180-5EF32-0HA0 at 415 V?","answer":"121 kA at 415 V AC, which is the value to use for selectivity and SCCR calculations at that voltage level."},{"question":"Where can I buy 3VA1180-5EF32-0HA0 and how do I get a price?","answer":"This MCCB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures are published here."},{"question":"What is the continuous current rating of 3VA1180-5EF32-0HA0 at 40 °C?","answer":"80 A at 40 °C ambient, with derating above 50 °C as listed in the thermal curve."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-5EF32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-5EF32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}