{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-6ED32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-6ED32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-6ED32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-6ED32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class H, Icu=70kA @ 415V, 3-pole, line protection TM210, FTFM, In=80A, Ir=80A fixed, Ii=10 x In, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1180-6ED32-0AA0-ZD00 is a 3-pole IEC frame 160 molded case circuit breaker in the 3VA1 series, rated for line protection with a TM210 thermal-magnetic trip unit. Fixed overload protection at Ir=80A (non-adjustable) and fixed short-circuit protection at Ii=10 x In (800 A magnetic pickup). The TM210 curve is a standard thermal-magnetic characteristic — thermal element handles overloads on a time-inverse curve, magnetic element clears hard shorts instantaneously at the Ii threshold. For a panel builder or MRO planner, the fixed Ir means this breaker is sized specifically for an 80 A continuous load; there is no adjustment band to dial down for a lighter feeder. The FTFM designation indicates the breaker includes internal accessories for remote signaling (fault, tripped, and main contact status) — useful for a PLC-based monitoring scheme without adding external aux contacts. ## Deployment context This variant includes a nut keeper kit and is specified for DC Power OEM applications in China — the nut keeper kit retains the mounting hardware during panel vibration or transport, a detail that saves field re-torque on a production line.","metaTitle":"Siemens 3VA1180-6ED32-0AA0-ZD00 Circuit Breaker, 80A, 70kA @","metaDescription":"Siemens 3VA1180-6ED32-0AA0-ZD00 IEC frame 160, H class Icu=70kA @ 415V, 3-pole, TM210, FTFM, In=80A, Ir=80A fixed, Ii=10xIn. Active lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/45877d9e25193b7318294325e0f15a10.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667858&mlfb=3VA1180-6ED32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-6ED32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1180-6ED32-0AA0-ZD00?","answer":"Submit an RFQ through this listing; pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is 3VA1180-6ED32-0AA0-ZD00's listed description?","answer":"It is a circuit breaker in the 3VA1 IEC frame 160, breaking capacity class H with Icu=70kA @ 415V, 3-pole, line protection TM210, FTFM, In=80A, overload protection Ir=80A fixed, short-circuit protection Ii=10 x In, includes a nut keeper kit, for DC Power OEM in China."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-6ED32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-6ED32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}