{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-6ED46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-6ED46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-6ED46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-6ED46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1180-6ED46-0AA0, molded case circuit breaker, 4-pole, 80 A (40 °C), TM210 thermal-magnetic release, interrupting capacity 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, 17 kA at 500/690 V.","salesMarkdown":"The 4-pole configuration handles three-phase-plus-neutral or three-phase with a switched neutral, common in North American and IEC distribution panels. Interrupting capacity is the headline: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V and 690 V. At 500 V and above the 17 kA rating still covers most motor-control-center bus faults, but verify against your transformer impedance if you're pushing 690 V. The 80 A rating holds flat from 40 °C to 50 °C, then steps down: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, 74 A at 70 °C. Dimensions are 130 mm high × 101.6 mm wide × 70 mm deep, so it fits a standard 4-pole MCCB footprint on DIN rail or a panel-mount base.","metaTitle":"Siemens 3VA1180-6ED46-0AA0 SENTRON MCCB, 80 A, 4-Pole, 220 k","metaDescription":"Siemens SENTRON 3VA1180-6ED46-0AA0 molded case circuit breaker, 80 A continuous, 4-pole, TM210 release, 220 kA at 240 V. Active production, available to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"80 A","at 45 °C":"80 A","at 50 °C":"80 A","at 55 °C":"78 A","at 60 °C":"77 A","at 65 °C":"75 A","at 70 °C":"74 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.2 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"80 A","design of I-trip / adjustable":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"without","operating voltage / at AC / rated value":"690 V","Max. rated operational voltage Ue with DC":"600 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"800 A","Adjustable response value current / li min.":"800 A","let-through energy characteristic / at 240 V":"DE_3VA1_0u1_80A_TM_line u starter_3u4p_240V","let-through energy characteristic / at 415 V":"DE_3VA1_0u1_80A_TM_line u starter_3u4p_415V","let-through energy characteristic / at 690 V":"DE_3VA1_0u1_80A_TM_line u starter_3u4p_690V","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","set values setting current (Ii) / for I-tripping":"10","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Tripping Characteristic / Of The Lower Tolerance Band":"AK_3VA1_0u1_80A_TM2_BuNuSuMuH_uT","Tripping Characteristic / Of The Upper Tolerance Band":"AK_3VA1_0u1_80A_TM2_BuNuSuMuH_oT","reference value setting current (Ii) / for I-tripping":"x In","reference value setting current (InN) / for N-tripping":"x In","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","type of value list setting current (Ii) / for I-tripping":"Fest","type of value list setting current (InN) / for N-tripping":"St","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1,5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f5ac4c3bf06fe547b03833be7c2f3bc7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=495596&mlfb=3VA1180-6ED46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-6ED46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1180-6ED46-0AA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."},{"question":"What is the interrupting capacity of this MCCB?","answer":"220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V."},{"question":"Does this breaker have an adjustable trip?","answer":"No — the TM210 release is fixed-characteristic; no adjustable I²t trip."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-6ED46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-6ED46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}