{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-6EF36-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-6EF36-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-6EF36-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-6EF36-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1180-6EF36-0JH0, molded case circuit breaker, 3-pole, 80 A rated at 40 °C, 220 kA breaking capacity at 240 V, line protection, with shunt trip and auxiliary switches.","salesMarkdown":"That 220 kA figure at 240 V means it handles very high available fault currents typical on the secondary of large step-down transformers or in high-capacity busway feeds; the 154 kA at 415 V and 121 kA at 440 V still cover most industrial service-entrance and sub-distribution scenarios. At 500 V and 690 V the rating drops to 17 kA, so if the line side is a 480 V or 600 V class system, verify the available fault current is under that threshold. ## Ratings that drive the fit The 80 A rating holds flat from 40 °C to 50 °C, then derates to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C — useful if the breaker lives in a hot enclosure or next to other heat sources. A shunt trip (STL) is built in for remote tripping. Dimensions: 130 mm high, 76.2 mm wide (3 in), 70 mm deep (2.76 in). ## Compliance documentation As a Siemens SENTRON MCCB, the 3VA1180-6EF36-0JH0 carries the usual compliance documentation: CE marking for the European market, UL/CSA listings for North America, and RoHS/REACH declarations. The exact certification numbers are on the nameplate and in the manufacturer's declaration pack available on request.","metaTitle":"Siemens 3VA1180-6EF36-0JH0 SENTRON MCCB, 80A, 220kA at 240V","metaDescription":"Siemens 3VA1180-6EF36-0JH0 SENTRON molded case circuit breaker, 80A rated at 40°C, 220kA breaking capacity at 240V. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"80 A","at 45 °C":"80 A","at 50 °C":"80 A","at 55 °C":"78 A","at 60 °C":"77 A","at 65 °C":"75 A","at 70 °C":"74 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.2 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11806EF360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=331495&mlfb=3VA1180-6EF36-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-6EF36-0JH0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA1180-6EF36-0JH0's breaking capacity at 415 V?","answer":"154 kA at 415 V, which covers most industrial 400 V class distribution. At 440 V it is 121 kA; at 500 V and 690 V it drops to 17 kA."},{"question":"Where can I buy 3VA1180-6EF36-0JH0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."},{"question":"Does 3VA1180-6EF36-0JH0 include a shunt trip?","answer":"Yes, a shunt trip (STL) is built in for remote tripping. It also has two auxiliary switches and one trip alarm switch (HQ). No undervoltage release or ground-fault monitoring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-6EF36-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-6EF36-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}