{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1180-6GE42-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1180-6GE42-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1180-6GE42-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1180-6GE42-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, 4-pole, 80A, breaking capacity class H Icu=70kA @ 415V, TM220 thermal-magnetic trip, ATFM, overload protection Ir=56A...80A, short-circuit protection Ii=10 x In.","salesMarkdown":"## Rated and Locked: 3VA1180-6GE42-0AA0-ZD00 The Siemens 3VA1180-6GE42-0AA0-ZD00 is a 4-pole IEC frame 160 circuit breaker with a breaking capacity class H rating of Icu=70kA at 415 V. The TM220 thermal-magnetic trip unit gives you overload protection adjustable from Ir=56 A to 80 A, and a fixed short-circuit pickup of Ii=10 x In. If you're specifying this into a panel, the 100% N-conductor protection and the nut keeper kit for DC Power OEM in China are part of the build; verify the keeper kit matches your bus-bar stack-up before the BOM locks. The TM220 thermal-magnetic trip provides inverse-time overload protection (the thermal element) and instantaneous magnetic trip at 10 x In (800 A for the 80 A rating). That 10 x In pickup is typical for motor branch circuits where you need to ride through inrush without nuisance tripping. The adjustable Ir (56 A to 80 A) lets you fine-tune the continuous current rating to the actual load, which is useful when the connected load is less than the breaker's In.","metaTitle":"Siemens 3VA1180-6GE42-0AA0-ZD00 Circuit Breaker, 80A, 70kA @","metaDescription":"Siemens 3VA1180-6GE42-0AA0-ZD00 IEC frame 160 circuit breaker, 80A, 70kA breaking capacity @ 415V, 4-pole, TM220. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a5781cf6f2db28aa8182254c40797329.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667865&mlfb=3VA1180-6GE42-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1180-6GE42-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for 3VA1180-6GE42-0AA0-ZD00?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this breaker?","answer":"Icu=70kA at 415 V, which is the maximum short-circuit current it can safely interrupt under IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1180-6GE42-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1180-6GE42-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}