{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-3EE32-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-3EE32-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-3EE32-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-3EE32-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1196-3EE32-0AB0, molded case circuit breaker, 4-pole, 100 A, 220 kA at 240 V, TM240 overcurrent release.","salesMarkdown":"Its interrupting capacity hits 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V — numbers that tell you this breaker is built for high-fault service entrance or main feeder duty where upstream coordination demands serious SCCR headroom. That 100 A holds flat from 40 °C up to 50 °C, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. It mounts into a panel via the SENTRON base adapter or direct screw fixing; no DIN-rail clip on this class. The 2 HP auxiliary switches (form C) are built in, so you get status feedback without an add-on module. If you need remote trip or monitoring, you'll add those as separate accessories. The N-conductor is protected at 100 % (full rating), which matters for 4-wire systems where the neutral carries load.","metaTitle":"Siemens 3VA1196-3EE32-0AB0 SENTRON MCCB, 100 A, 220 kA at 24","metaDescription":"Siemens SENTRON 3VA1196-3EE32-0AB0 molded case circuit breaker, 100 A rated, 220 kA at 240 V, 4-pole, TM240 release. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Width [in]":"4 in","Trip indicator":"No","Number of poles":"4","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Design of the N-conductor protection":"100%","Max. rated operational voltage Ue with DC":"600 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"500 A","Adjustable response value current / lr min.":"70 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=694832&mlfb=3VA1196-3EE32-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-3EE32-0AB0/alternatives.json"},"ai":{"faq":[{"question":"What are the key interrupting ratings for the 3VA1196-3EE32-0AB0?","answer":"At 240 V it interrupts 220 kA, at 415 V it interrupts 154 kA, at 440 V it interrupts 121 kA, and at 500 V or 690 V it interrupts 17 kA."},{"question":"Where can I buy the 3VA1196-3EE32-0AB0 and how is it quoted?","answer":"This breaker is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — no stock figures or lead-time numbers are published here."},{"question":"Does the 3VA1196-3EE32-0AB0 include a trip indicator or undervoltage release?","answer":"No. It has no trip indicator, no undervoltage release, no shunt trip, and no ground-fault module — it is a plain line-protection MCCB with a TM240 release and 2 HP auxiliary switches."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-3EE32-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-3EE32-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}