{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-3EF32-0AF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-3EF32-0AF0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-3EF32-0AF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-3EF32-0AF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1196-3EF32-0AF0, molded case circuit breaker, 3-pole, 16 A, TM240 overcurrent release, 75.6 kA at 240 V, 70 mm depth, 76.2 mm width, 130 mm height.","salesMarkdown":"Breaking capacity hits 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V, covering most industrial distribution panels up to 690 V line-to-line. Thermal derating is flat to 50 °C at 16 A, then steps down to 15.36 A at 55 °C, 15.04 A at 60 °C, 14.72 A at 65 °C, and 14.4 A at 70 °C. ## Integration Notes IP40 on the front — suitable for clean indoor panels; not rated for washdown environments. The TM240 release has a fixed thermal time delay (tr max. 1 s at 6× Iu per the spec). No phase-failure detection inside — if that's required, add an external phase monitor or step up to a 3VA variant with electronic release. Designed to IEC 60947-2 (MCCB standard). The manufacturer provides RoHS and REACH declarations as standard; UL/CSA listing depends on the specific variant — verify the nameplate marking for the exact certification marks on the unit received.","metaTitle":"Siemens 3VA1196-3EF32-0AF0 SENTRON MCCB, 16 A, 3-pole, 75.6","metaDescription":"Siemens 3VA1196-3EF32-0AF0 SENTRON molded case circuit breaker, 16 A rated, 3-pole, breaking capacity up to 75.6 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 690 V":"10.5 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"15.36 A","at 60 °C":"15.04 A","at 65 °C":"14.72 A","at 70 °C":"14.4 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"16 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"16 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"160 A","Adjustable response value current / lr min.":"11 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=200209&mlfb=3VA1196-3EF32-0AF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-3EF32-0AF0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1196-3EF32-0AF0?","answer":"Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-3EF32-0AF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-3EF32-0AF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}