{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-3EF32-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-3EF32-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-3EF32-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-3EF32-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1196-3EF32-0DA0, Molded case circuit breaker, 3-pole, 16 A, 75.6 kA at 240 V, TM240 overcurrent release, undervoltage release.","salesMarkdown":"## Siemens SENTRON 3VA1196-3EF32-0DA0 — Line Protection MCCB with Undervoltage Release The Siemens SENTRON 3VA1196-3EF32-0DA0 is a 3-pole molded case circuit breaker (MCCB) designed for line protection, carrying a 16 A continuous rating that holds flat from 40 °C through 55 °C before derating to 15 A at 65 °C and 70 °C. Its interrupting capacity reaches 75.6 kA at 240 VAC, 52.5 kA at 415 VAC, 32 kA at 440 VAC, and 11.9 kA at both 500 VAC and 690 VAC — figures that give the panel designer headroom for high-fault downstream coordination without cascading upstream. The unit ships with a factory-fitted undervoltage release (UVR) of the TM240 type, so it drops the load on loss of control voltage — a standard requirement for emergency-stop circuits and machine-guarding zones where a voltage dip must clear the power path. Rated insulation voltage is 800 V, and the operating temperature range spans -25 °C to 70 °C, with storage from -40 °C to 80 °C. ## Physical Fit & Panel Integration Dimensions are 130 mm high, 76.2 mm wide, and 70 mm deep — a standard SENTRON 3VA footprint that mounts directly onto DIN rail or a mounting plate without adapters. Maximum power loss is 13.1 W, which factors into the enclosure thermal budget when grouping several breakers in a sealed panel. ## Key Functional Notes","metaTitle":"Siemens 3VA1196-3EF32-0DA0 SENTRON MCCB, 16 A, 75.6 kA at 24","metaDescription":"Siemens SENTRON 3VA1196-3EF32-0DA0 molded case circuit breaker, 3-pole, 16 A rated, 75.6 kA breaking capacity at 240 VAC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.1 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11963EF320AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=11179&mlfb=3VA1196-3EF32-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-3EF32-0DA0/alternatives.json"},"ai":{"faq":[{"question":"Does the 3VA1196-3EF32-0DA0 include an undervoltage release?","answer":"Yes, it is fitted with an undervoltage release (UVR) of the TM240 design."},{"question":"What are the physical dimensions of the 3VA1196-3EF32-0DA0?","answer":"Height is 130 mm, width is 76.2 mm, and depth is 70 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-3EF32-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-3EF32-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}