{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-3EF32-0DH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-3EF32-0DH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-3EF32-0DH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-3EF32-0DH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1196-3EF32-0DH0, 3-pole molded case circuit breaker (MCCB), 16 A rated at 40 °C, 75.6 kA breaking at 240 V AC, with undervoltage release and auxiliary switches.","salesMarkdown":"## Siemens SENTRON 3VA1196-3EF32-0DH0 — 3-Pole MCCB with Undervoltage Release Breaking capacity hits 75.6 kA at 240 V AC, stepping down to 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V — so it handles high-fault industrial feeds without cascading upstream. At 130 mm tall, 76.2 mm wide, and 70 mm deep, this 3-pole MCCB fits a standard 3-module-wide DIN-rail footprint. ## Thermal Derating and Ambient Range At 60 °C it derates to 15 A, and stays at 15 A through 70 °C. That's a clean, predictable derating curve — no surprise drop at 50 °C like some older MCCB lines.","metaTitle":"Siemens SENTRON 3VA1196-3EF32-0DH0 MCCB, 3-Pole 16A, 75.6kA","metaDescription":"Siemens SENTRON 3VA1196-3EF32-0DH0 molded case circuit breaker, 3-pole, 16A rated current, 75.6kA breaking capacity at 240V AC. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.1 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11963EF320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=68385&mlfb=3VA1196-3EF32-0DH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-3EF32-0DH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1196-3EF32-0DH0 and get a price?","answer":"This MCCB is sourced through independent distribution and quoted to order against an RFQ. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is the depth of 3VA1196-3EF32-0DH0?","answer":"Depth is 70 mm (2.76 in). Width is 76.2 mm (3 in), height is 130 mm (5.12 in)."},{"question":"What breaking capacity does 3VA1196-3EF32-0DH0 have at 240 V?","answer":"Breaking capacity is 75.6 kA at 240 V AC. At 415 V it's 52.5 kA, at 440 V it's 32 kA, and at 500 V / 690 V it's 11.9 kA."},{"question":"Does 3VA1196-3EF32-0DH0 include an undervoltage release?","answer":"Yes, it comes with an undervoltage release (UVR) plus a factory-installed auxiliary switch block: 2 auxiliary switches and 1 trip alarm switch HQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-3EF32-0DH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-3EF32-0DH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}