{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-3GD42-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-3GD42-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-3GD42-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-3GD42-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160 circuit breaker, breaking capacity class N, Icu=25kA @ 415V, 4-pole, line protection TM210, FTFM, In=16A, Ir=16A, Ii=20 x In, N conductor protection 100%, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1196-3GD42-0AA0-ZD00 is a 4-pole IEC frame 160 circuit breaker with breaking capacity class N, rated Icu=25kA at 415V. The N conductor is protected at 100%. For continuous load, the 16A Ir (fixed) sets the thermal pickup; don't plan to adjust it. The Ii=20 x In means magnetic trip happens at 320A, so it'll ride through motor inrush on smaller loads but still clear a hard fault fast. The 4-pole construction with 100% N protection is typical for 3-phase + neutral systems where you can't allow the neutral to open under fault. ## Deployment context This breaker mounts in a standard DIN-rail enclosure or panel — the 3VA1 frame is designed for 35mm DIN rail. The nut keeper kit (included per the order code suffix) is a detail for DC Power OEM builds in China, where the breaker gets bolted into a sub-panel rather than snapped onto the rail. Keep that in mind if you're swapping into a standard DIN-rail panel: the kit may need to be removed or the mounting holes used instead of the rail clip.","metaTitle":"Siemens 3VA1196-3GD42-0AA0-ZD00 Circuit Breaker, 25kA @ 415V","metaDescription":"Siemens 3VA1196-3GD42-0AA0-ZD00 IEC frame 160 circuit breaker, breaking capacity class N, Icu=25kA @ 415V, 4-pole, In=16A, Ir=16A, Ii=20 x In. Active lifecycle. Quoted to order aga","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/147a00a8e82cf95f7f70e2497f691d07.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667873&mlfb=3VA1196-3GD42-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-3GD42-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"The breaking capacity class N gives Icu=25kA at 415V AC."},{"question":"Where can I buy 3VA1196-3GD42-0AA0-ZD00?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-3GD42-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-3GD42-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}