{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-4ED16-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-4ED16-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-4ED16-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-4ED16-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1196-4ED16-0AA0, 1-pole molded case circuit breaker, 16 A rated current, 75.6 kA breaking capacity at 240 V AC, TM210 thermal-magnetic release, IP40 front protection.","salesMarkdown":"## 1-pole SENTRON MCCB with TM210 release Its 75.6 kA breaking capacity at 240 V AC handles high-fault scenarios typical of industrial distribution panels; at 415 V AC the rating drops to 9 kA, which still covers most secondary feeder faults in a 400 V system. The single-pole form factor (25.4 mm wide) fits standard DIN-rail or panel-mount enclosures where branch-circuit protection is needed without occupying multiple module slots. ## Thermal-magnetic curve and derating The TM210 release holds the full 16 A rating from 40 °C up to 55 °C, then derates to 15 A at 60 °C through 70 °C. That flat thermal curve means the breaker can be applied in a warm cabinet without losing capacity until the ambient exceeds 55 °C. Maximum power loss is 3.53 W, low enough to avoid significant heat buildup inside a sealed enclosure. ## Physical integration At 70 mm deep, 25.4 mm wide, and 130 mm tall, the 3VA1196-4ED16-0AA0 occupies a single-pole width on the DIN rail.","metaTitle":"Siemens 3VA1196-4ED16-0AA0 SENTRON MCCB, 1-Pole 16A, 75.6kA","metaDescription":"Siemens 3VA1196-4ED16-0AA0 SENTRON molded case circuit breaker, 1-pole, 16A rated current, 75.6kA breaking capacity at 240V AC. Current production. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"25.4 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"9 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"1 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"1","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"3.53 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"16 A","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"415 V","Max. rated operational voltage Ue with DC":"125 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"No","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1,5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b9bd9c736b41bce48a75cdfbf71ec1d9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=486211&mlfb=3VA1196-4ED16-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-4ED16-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1196-4ED16-0AA0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is the breaking capacity of this MCCB at 240 V and 415 V?","answer":"The 3VA1196-4ED16-0AA0 is rated for 75.6 kA at 240 V AC and 9 kA at 415 V AC, covering high-fault industrial distribution and secondary feeder protection."},{"question":"What type of overcurrent release does this breaker use?","answer":"It uses a TM210 thermal-magnetic release, providing both overload (thermal) and short-circuit (magnetic) protection in a single mechanism."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-4ED16-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-4ED16-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}