{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-4ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-4ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-4ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-4ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1196-4ED22-0AA0, 2-pole molded case circuit breaker, 16 A rated current, 121 kA breaking capacity at 240 V AC, TM210 release, IP40 front.","salesMarkdown":"## Siemens 3VA1196-4ED22-0AA0 — 2-Pole 16 A MCCB with 121 kA Breaking Capacity The Siemens 3VA1196-4ED22-0AA0 is a 2-pole SENTRON molded case circuit breaker (MCCB) rated 16 A continuous at 40 °C, with a TM210 thermal-magnetic overcurrent release. Its interrupting capacity is 121 kA at 240 V AC and 75.6 kA at 415 V AC — enough for high-fault utility feeds or transformer secondaries where a standard MCB would weld. At 121 kA (240 V AC) this MCCB sits in the high-interrupting tier of the 3VA family. Thermal pickup at 1.05× In, magnetic instantaneous at 10× In typical for this design. The 3VA1196-4ED22-0AA0 measures 130 mm high × 50.8 mm wide × 70 mm deep. The 50.8 mm width is two standard 25.4 mm module spaces on a DIN rail — same footprint as a 2-pole MCB, so it drops into existing panel layouts without re-drilling. If you need those, the 3VA platform accepts clip-on accessories, but verify compatibility with this specific variant — the TM210 base unit ships bare.","metaTitle":"Siemens 3VA1196-4ED22-0AA0 SENTRON MCCB, 2-Pole, 16 A, 121 k","metaDescription":"Siemens 3VA1196-4ED22-0AA0 SENTRON MCCB, 2-pole, 16 A rated at 40 °C, 121 kA breaking at 240 V AC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"2","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.06 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","operating voltage / at DC / rated value":"250 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fb6ae6d29c44a70796b063ae62352722.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=274559&mlfb=3VA1196-4ED22-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-4ED22-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1196-4ED22-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"What is the breaking capacity of 3VA1196-4ED22-0AA0?","answer":"121 kA at 240 V AC and 75.6 kA at 415 V AC, making it suitable for high-fault industrial feeds."},{"question":"Will 3VA1196-4ED22-0AA0 drop into a panel specified around 3VA1110-5ED32-0AA0?","answer":"Both are 2-pole SENTRON MCCBs on the same 50.8 mm DIN-rail footprint, so physical fit is identical. The key difference is breaking capacity and trip curve — verify the 3VA1110-5ED32-0AA0's ratings against your fault study before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-4ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-4ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}