{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-4EF32-0AD0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-4EF32-0AD0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-4EF32-0AD0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-4EF32-0AD0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1196-4EF32-0AD0, 3-pole molded case circuit breaker, 16 A rated current, 121 kA breaking capacity at 240 V AC, line protection design.","salesMarkdown":"It carries a rated current of 16 A up to 55 °C, derating to 15 A at 60 °C and above — so in a warm cabinet you lose 1 A of headroom above 55 °C ambient. Breaking capacity is the headline here: 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. The overcurrent release is a TM240 thermal-magnetic type, and the breaker is fitted with three auxiliary switches HQ. Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a 3-pole MCCB footprint that fits standard Siemens SENTRON mounting plates and DIN-rail adapters.","metaTitle":"Siemens 3VA1196-4EF32-0AD0 SENTRON MCCB, 16 A, 121 kA at 240","metaDescription":"Siemens SENTRON 3VA1196-4EF32-0AD0 molded case circuit breaker, 3-pole, 16 A rated, 121 kA breaking capacity at 240 V AC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11964EF320AA0","Design Of The Auxiliary Switch":"3 auxiliary switches HQ","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=420944&mlfb=3VA1196-4EF32-0AD0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-4EF32-0AD0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at 240 V?","answer":"121 kA at 240 V AC, with 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V."},{"question":"Where can I buy 3VA1196-4EF32-0AD0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Does this breaker include an undervoltage release or ground-fault monitoring?","answer":"No. This variant has no undervoltage release and no ground-fault monitoring. It is a line-protection MCCB with a TM240 thermal-magnetic release and three auxiliary switches HQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-4EF32-0AD0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-4EF32-0AD0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}