{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-4EF32-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-4EF32-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-4EF32-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-4EF32-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160 circuit breaker, breaking capacity class S, 3-pole, line protection TM240, In=16A, Icu=36kA @ 415V, with undervoltage release (UVR) 24V DC.","salesMarkdown":"Short-circuit pickup Ii is fixed at 10 to 20 times In (160 to 320 A), which is typical for line protection — it clears hard faults fast but rides through motor inrush. The breaker mounts in a standard IEC frame 160 footprint — three-pole, with a nut keeper kit included for secure terminal clamping on busbars or cable lugs. The 24 V DC undervoltage release coil draws power from the control circuit; verify that your 24 V supply can hold the coil energised (typically around 5 W holding) and that the UVR is wired to a normally-closed safety contact that drops the breaker on a trip condition. The TM240 dial is accessible on the front face for adjusting Ir without removing the cover.","metaTitle":"Siemens 3VA1196-4EF32-0BA0 Circuit Breaker, 16A, 36kA @ 415V","metaDescription":"Siemens 3VA1196-4EF32-0BA0 IEC frame 160 circuit breaker, 3-pole, 16A, 36kA breaking capacity @ 415V. TM240 overload, UVR 24V DC. Current lifecycle stage. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=336110&mlfb=3VA1196-4EF32-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-4EF32-0BA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1196-4EF32-0BA0 and get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this breaker?","answer":"Icu = 36 kA at 415 V, which is the maximum fault current it can safely interrupt once under IEC 60947-2."},{"question":"What does the TM240 trip unit adjust to?","answer":"Overload protection Ir is adjustable from 11 A to 16 A; short-circuit protection Ii is fixed at 10 to 20 times In (160 to 320 A)."},{"question":"Does this breaker include an undervoltage release?","answer":"Yes, a 24 V DC undervoltage release (UVR) is built in, allowing the breaker to trip on loss of control voltage."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-4EF32-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-4EF32-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}