{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-4EF32-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-4EF32-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-4EF32-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-4EF32-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1196-4EF32-0DA0, molded case circuit breaker, 3-pole, 16 A rated at 40 °C, 121 kA interrupting at 240 V, line protection with undervoltage release.","salesMarkdown":"## Siemens 3VA1196-4EF32-0DA0 — SENTRON MCCB for Line Protection It carries a 121 kA interrupting capacity at 240 V, dropping to 75.6 kA at 415 V and 52.5 kA at 440 V — figures that govern its selectivity in high-fault-current distribution panels. The 16 A rating holds across ambient temperatures from 40 °C to 55 °C, derating to 15 A at 60 °C and above — important for panels with limited airflow or elevated internal heat rise. Power loss is 13.1 W maximum, a figure to account for in enclosure thermal calculations. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a 3-inch-wide footprint that fits standard Siemens SENTRON panelboard mounting. ## Integration — DIN Rail and Panel Fit The 3VA1196-4EF32-0DA0 mounts on DIN rail (standard 35 mm) or directly to a panel via the supplied basic switch (order code 3VA11964EF320AA0). The undervoltage release coil requires a separate control voltage — verify polarity and suppression for the specific UVR variant.","metaTitle":"Siemens 3VA1196-4EF32-0DA0 SENTRON MCCB, 16 A, 3-Pole, 121 k","metaDescription":"Siemens 3VA1196-4EF32-0DA0 SENTRON molded case circuit breaker, 16 A rated, 3-pole, 121 kA interrupting at 240 V. Line protection with undervoltage release. Active production, quot","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.1 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11964EF320AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=250938&mlfb=3VA1196-4EF32-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-4EF32-0DA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA1196-4EF32-0DA0 at 240 V?","answer":"121 kA at 240 V, with 75.6 kA at 415 V and 52.5 kA at 440 V."},{"question":"Where can I buy 3VA1196-4EF32-0DA0 and how is it quoted?","answer":"Sourced through independent distribution and quoted to order against an RFQ — availability and current pricing confirmed at quote time."},{"question":"Does 3VA1196-4EF32-0DA0 include an undervoltage release?","answer":"Yes, it includes an undervoltage release (UVR) designed as an auxiliary release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-4EF32-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-4EF32-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}