{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-4EF36-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-4EF36-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-4EF36-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-4EF36-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160 circuit breaker, breaking capacity class S, 3-pole, line protection TM240, In=16A, Icu=36kA @ 415V AC, with undervoltage release 120-127V AC, 2 auxiliary switches HQ, 1 trip alarm switch HQ, clamp connection.","salesMarkdown":"The Siemens 3VA1196-4EF36-0CH0 is an IEC frame 160 molded-case circuit breaker in the 3VA1 series, rated In=16A with a TM240 thermal-magnetic trip unit. ## Trip settings and auxiliary wiring Overload protection Ir is adjustable from 11A to 16A, letting you fine-tune the thermal pickup to the actual load without swapping the breaker body. Short-circuit magnetic pickup Ii is fixed at 10 to 20 times In (160A to 320A), which is a standard range for motor-starting inrush coordination.","metaTitle":"Siemens 3VA1196-4EF36-0CH0 Circuit Breaker, 16A, 36kA @ 415V","metaDescription":"Siemens 3VA1196-4EF36-0CH0 IEC frame 160 circuit breaker, 3-pole, 16A, Icu=36kA @ 415V. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=427491&mlfb=3VA1196-4EF36-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-4EF36-0CH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1196-4EF36-0CH0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ to confirm current availability and pricing."},{"question":"What are the key ratings of 3VA1196-4EF36-0CH0?","answer":"It is a 3-pole IEC frame 160 breaker with In=16A, Icu=36kA @ 415V AC, thermal overload adjustable 11A-16A, magnetic pickup 10-20x In, and includes an undervoltage release (120-127V AC), 2 auxiliary switches, and 1 trip alarm switch."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-4EF36-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-4EF36-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}