{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-5ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-5ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-5ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-5ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1196-5ED22-0AA0, 2-pole molded case circuit breaker, 16 A rated continuous current, 187 kA breaking capacity at 240 V AC, TM210 release, line protection.","salesMarkdown":"Its rated continuous current of 16 A holds flat across ambient temperatures up to 55 °C, then derates to 15 A at 60 °C and above, so in a warm panel you lose 1 A of headroom. The overcurrent release is a TM210 — a thermal-magnetic fixed-trip design. Thermal element handles overloads (the 16 A continuous rating); magnetic element handles short-circuit instantaneous trip. The 2-pole configuration suits single-phase or two-phase line protection; for three-phase loads you'd spec a 3-pole sibling. Dimensions: 130 mm height, 50.8 mm width (2 inches — fits a standard 2-pole MCCB slot), 70 mm depth. Front protection is IP40 — tools and fingers won't reach live parts, but the enclosure itself must be rated for the overall panel IP.","metaTitle":"Siemens 3VA1196-5ED22-0AA0 SENTRON MCCB, 2-Pole, 16 A, 187 k","metaDescription":"Siemens 3VA1196-5ED22-0AA0 SENTRON molded case circuit breaker, 2-pole, 16 A rated, 187 kA breaking capacity at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","Height":"130 mm","Maximum":"320 A","Minimum":"320 A","at 240 V":"187 kA","at 415 V":"121 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"2","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.06 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"16 A","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","operating voltage / at DC / rated value":"250 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/07665b4959c72ae25682c04eff98007a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=694662&mlfb=3VA1196-5ED22-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-5ED22-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1196-5ED22-0AA0?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this MCCB?","answer":"187 kA at 240 V AC and 121 kA at 415 V AC."},{"question":"What is the continuous current rating and how does it derate with temperature?","answer":"Rated 16 A continuous. It holds 16 A up to 55 °C, then derates to 15 A at 60 °C and above."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-5ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-5ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}