{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-6ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-6ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-6ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-6ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1196-6ED32-0AA0, molded case circuit breaker, 3-pole, 16 A (40 °C), 220 kA at 240 V, TM210 release, line protection, IP40 front.","salesMarkdown":"At 415 V the rating drops to 154 kA, at 440 V to 121 kA, and at 500 V or 690 V it holds at 17 kA — the steep fall-off above 440 V is typical of a compact MCCB frame and matters if your secondary is a 480 V or 600 V class transformer. That keeps the BOM simple and the part interchangeable with older panels that expect a non-electronic MCCB. No official successor order code has been published for this part; the 3VA1 platform remains the current SENTRON MCCB generation for line-protection applications. The 3VA1196-6ED32-0AA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a 3-pole MCCB footprint that drops into standard SENTRON 3VA1 mounting bases and busbar systems. ## Ambient derating and operating range The 16 A rating holds flat from 40 °C through 55 °C; at 60 °C it derates to 15 A and stays there through 70 °C. That means no capacity loss in most ventilated panels, but a sealed enclosure near other heat sources may push the effective rating down. The storage minimum is the more restrictive number for warehousing — keep it above -40 °C and the breaker will not suffer mechanical damage before installation.","metaTitle":"Siemens 3VA1196-6ED32-0AA0 SENTRON MCCB, 16 A, 220 kA","metaDescription":"Siemens 3VA1196-6ED32-0AA0 SENTRON molded case circuit breaker, 16 A rated at 40 °C, 220 kA breaking capacity at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=474360&mlfb=3VA1196-6ED32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-6ED32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA1196-6ED32-0AA0 drop into a panel specified around 3VA1110-5ED32-0AA0 without rewiring?","answer":"Both are 3-pole SENTRON 3VA1 frame MCCBs with the same 130 mm height, 76.2 mm width, and 70 mm depth, so the mechanical footprint and busbar connection pattern are identical. The electrical ratings differ — the 3VA1196-6ED32-0AA0 carries a 16 A TM210 release versus the 3VA1110-5ED32-0AA0's lower ampacity — so verify the load current and coordination study before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-6ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-6ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}