{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-6EF32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-6EF32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-6EF32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-6EF32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1196-6EF32-0CC0, molded case circuit breaker, 3-pole, 16 A (40 °C), 220 kA at 240 V, undervoltage release, 2 auxiliary switches HQ, line protection.","salesMarkdown":"The Siemens SENTRON 3VA1196-6EF32-0CC0 is a 3-pole molded case circuit breaker (MCCB) rated 16 A continuous at 40 °C, with a massive 220 kA interrupting capacity at 240 VAC. The 16 A rating holds steady from 40 °C up to 55 °C, then derates to 15 A at 60 °C and above — so in a warm panel you still get full current up to 55 °C, which is better than many breakers that start derating at 40 °C. The interrupting capacity drops as voltage rises: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V or 690 V. The auxiliary switches give you status feedback (open/closed) for PLC or indicator lights without needing an add-on module. ## Where this MCCB fits in a panel This is a DIN-rail-mount MCCB (70 mm deep, 76.2 mm wide, 130 mm tall), so it clips onto standard 35 mm DIN rail inside a distribution board or control panel. The 3-pole format handles three-phase circuits. Because it's a line-protection design, it's the right choice for the main incoming breaker or a branch feeder protecting cables and busbars — not for direct motor starting (that needs a motor-protective breaker with a different trip curve).","metaTitle":"Siemens 3VA1196-6EF32-0CC0 SENTRON MCCB, 16 A, 220 kA at 240","metaDescription":"Siemens 3VA1196-6EF32-0CC0 SENTRON molded case circuit breaker, 3-pole, 16 A rated at 40 °C, 220 kA interrupting at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.1 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11966EF320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=308664&mlfb=3VA1196-6EF32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-6EF32-0CC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1196-6EF32-0CC0 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here."},{"question":"What is the interrupting capacity of 3VA1196-6EF32-0CC0 at 240 V?","answer":"It is rated 220 kA at 240 VAC, which is very high — suitable for panels with high available fault current."},{"question":"Does 3VA1196-6EF32-0CC0 include an undervoltage release?","answer":"Yes, it comes with an undervoltage release (UVR) as standard, plus two auxiliary switches (HQ design)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-6EF32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-6EF32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}