{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-6EF32-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-6EF32-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-6EF32-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-6EF32-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1196-6EF32-0DA0, molded case circuit breaker, 3-pole, 16 A, TM240 overcurrent release, 220 kA at 240 V, IP40 front.","salesMarkdown":"Its interrupting capacity hits 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V — numbers that tell you this breaker is built for high-fault panels where a standard MCB would weld shut. The 16 A rating holds flat from 40 °C to 50 °C, then derates to 15.36 A at 55 °C and 14.4 A at 70 °C. Width 76.2 mm (3-pole), depth 70 mm, height 130 mm. The 3VA family uses a common mounting pattern, so swapping from another 3VA frame is straightforward — same DIN rail clip, same busbar pitch. The undervoltage release is present, so verify coil voltage matches your control circuit before wiring.","metaTitle":"Siemens SENTRON 3VA1196-6EF32-0DA0 MCCB, 16 A, 220 kA at 240","metaDescription":"Siemens SENTRON 3VA1196-6EF32-0DA0 molded case circuit breaker, 3-pole, 16 A, TM240 release, 220 kA at 240 V. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 690 V":"17 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"15.36 A","at 60 °C":"15.04 A","at 65 °C":"14.72 A","at 70 °C":"14.4 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"16 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"16 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"160 A","Adjustable response value current / lr min.":"11 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=298469&mlfb=3VA1196-6EF32-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-6EF32-0DA0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA1196-6EF32-0DA0's listed depth (70 mm) on this component line?","answer":"The depth is 70 mm. That's the body depth excluding any protruding handle or terminals — typical for the 3VA frame."},{"question":"What is 3VA1196-6EF32-0DA0's listed width (76.2 mm) on this component line?","answer":"The width is 76.2 mm for the 3-pole version. That's a standard 3VA 3-pole width, matching the busbar pitch for 3-pole SENTRON breakers."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-6EF32-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-6EF32-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}