{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-6EF42-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-6EF42-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-6EF42-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-6EF42-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class H, Icu=70kA @ 415V, 4-pole, line protection TM240 ATAM, In=16A, overload Ir=11-16A, short-circuit Ii=10-20xIn, N conductor unprotected, nut keeper kit for DC Power OEM in China.","salesMarkdown":"## What the 70 kA breaking capacity means for your panel The 3VA1196-6EF42-0AA0-ZD00 is a Siemens 3VA1 IEC frame 160 molded-case circuit breaker with a class H interrupting rating of Icu=70 kA at 415 VAC. ## Overload and short-circuit protection settings The TM240 ATAM trip unit provides thermal-magnetic protection with an adjustable overload current Ir from 11 A to 16 A (In=16 A fixed), and a short-circuit pickup Ii adjustable from 10 to 20 times In. That 10-20x In range gives selectivity headroom for motor-starting inrush or transformer magnetizing currents — set the magnetic pickup high enough to ride through the transient, low enough to catch a bolted fault. The ATAM designation means it includes an alarm switch for the trip event, useful for remote fault annunciation in an unmanned panel.","metaTitle":"Siemens 3VA1196-6EF42-0AA0-ZD00 Circuit Breaker, 70kA @ 415V","metaDescription":"Siemens 3VA1196-6EF42-0AA0-ZD00 IEC frame 160 circuit breaker, breaking capacity class H Icu=70kA @ 415V, 4-pole, TM240 ATAM overload Ir=11-16A, short-circuit Ii=10-20xIn. Current","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cf9c45e0d8b24b58aea34aa6bffd1d0f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667899&mlfb=3VA1196-6EF42-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-6EF42-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"What does the Icu=70kA @ 415V rating mean for this breaker?","answer":"Icu=70 kA at 415 V is the ultimate short-circuit breaking capacity — the maximum fault current the breaker can safely interrupt once without needing replacement. Class H is Siemens' designation for this high-breaking level, suitable for high-fault industrial mains."},{"question":"What are the adjustable trip settings on this 3VA1 breaker?","answer":"The TM240 ATAM thermal-magnetic trip unit allows overload current Ir adjustment from 11 A to 16 A (In=16 A), and short-circuit pickup Ii from 10 to 20 times In. The ATAM suffix includes an integrated alarm switch for trip indication."},{"question":"Where can I buy 3VA1196-6EF42-0AA0-ZD00?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an inquiry for a firm quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-6EF42-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-6EF42-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}