{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1196-6GD46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1196-6GD46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1196-6GD46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1196-6GD46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON molded case circuit breaker, 3VA1196-6GD46-0AA0, 4-pole, 16 A rated, TM210 release, breaking capacity 220 kA at 240 V, 154 kA at 415 V, IP40 front.","salesMarkdown":"## Breaking capacity and thermal performance Its interrupting capacity is the headline number: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and still 17 kA at 690 V. At 415 V the 154 kA rating covers most industrial mains where the transformer impedance alone won't limit fault current below that level. At 60 °C it derates to 15 A, same at 65 °C and 70 °C. That's a tight thermal curve — the breaker doesn't shed much capacity until you're well above typical panel ambient. The TM210 release is a thermal-magnetic trip with fixed thermal and magnetic settings, so no field adjustment for the overload pickup; you select the breaker for the load current. The 3VA1196-6GD46-0AA0 measures 70 mm deep, 101.6 mm wide, 130 mm high — a 4-pole MCCB that fits standard Siemens SENTRON mounting footprints.","metaTitle":"Siemens SENTRON 3VA1196-6GD46-0AA0 MCCB, 16 A, 4-Pole, 220 k","metaDescription":"Siemens SENTRON 3VA1196-6GD46-0AA0 molded case circuit breaker, 16 A rated, 4-pole, TM210 release. Breaking capacity 220 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"16 A","Minimum":"16 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=269874&mlfb=3VA1196-6GD46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1196-6GD46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1196-6GD46-0AA0 at different voltages?","answer":"220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V."},{"question":"Where can I buy 3VA1196-6GD46-0AA0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What are the physical dimensions of 3VA1196-6GD46-0AA0?","answer":"Depth 70 mm, width 101.6 mm, height 130 mm."},{"question":"What compliance documentation is available for this breaker?","answer":"The part carries Siemens SENTRON brand documentation including RoHS and REACH compliance data per standard Siemens industrial product documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1196-6GD46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1196-6GD46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}