{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1216-4EE32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1216-4EE32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1216-4EE32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1216-4EE32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VA1216-4EE32-0AA0, molded case circuit breaker, 3-pole, 160 A continuous, TM220 thermal-magnetic release, breaking capacity 121 kA at 240 V AC.","salesMarkdown":"At 240 V it interrupts 121 kA; at 415 V it handles 75.6 kA; at 440 V it drops to 52.5 kA; at 500 V it's 17 kA; at 690 V it's 11.9 kA. At 55 °C it drops to 156 A; at 60 °C to 151 A; at 65 °C to 147 A; at 70 °C to 142 A. If your enclosure runs hot — say a non-ventilated panel near a furnace line — size the load for the 70 °C figure, not the nameplate. Dimensions are 105 mm wide, 158 mm high, 70 mm deep. If you need remote trip or status feedback, you're looking at a different suffix in the 3VA family. ## Compliance documentation As a SENTRON product, the 3VA series carries CE marking for the European market and UL/CSA listings for North American installations. RoHS and REACH declarations are standard with the manufacturer's documentation package. The specific certification numbers appear on the nameplate and in the device manual linked under Service & Support.","metaTitle":"SENTRON 3VA1216-4EE32-0AA0 Molded Case Circuit Breaker, 160","metaDescription":"SENTRON 3VA1216-4EE32-0AA0 3-pole MCCB rated 160 A continuous with TM220 release. Breaking capacity 121 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"105 mm","title":"3VA1216-4EE32-0AA0","Height":"158 mm","Maximum":"1 600 A","Minimum":"1 600 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"17 kA","at 690 V":"11.9 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"156 A","at 60 °C":"151 A","at 65 °C":"147 A","at 70 °C":"142 A","Depth [In]":"2.76 in","Width [In]":"4.13 in","Height [In]":"6.22 in","description":"circuit breaker 3VA1 IEC frame 250 breaking capacity class S Icu=36kA @ 415V 3-pole, line protection TM220, ATFM, In=160A overload protection Ir=112A...160A short-circuit protection Ii=10 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"33 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM220","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/207b48ed507d4316da54ff19530c766d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=690156&mlfb=3VA1216-4EE32-0AA0"},"ai":{"faq":[{"question":"What is 3VA1216-4EE32-0AA0's listed depth?","answer":"70 mm (2.76 in). That is the body depth excluding any protruding handle or terminal covers."},{"question":"What compliance documentation does SENTRON provide for 3VA1216-4EE32-0AA0?","answer":"The manufacturer provides CE marking, UL/CSA listings, RoHS and REACH declarations as standard. The specific certification numbers are printed on the device nameplate and detailed in the 3VA molded case circuit breaker device manual available under Service & Support."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1216-4EE32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1216-4EE32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}