{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1216-6EF32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1216-6EF32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1216-6EF32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1216-6EF32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 250 MCCB, 3-pole, breaking capacity class H Icu=70 kA @ 415 V, TM240 thermal-magnetic trip unit, In=160 A, Ir=112…160 A, Ii=5…10 x In, with nut keeper kit for DC Power OEM in China.","salesMarkdown":"The 3VA1216-6EF32-0AA0-ZD00 is a Siemens 3VA1 IEC frame 250 molded-case circuit breaker, 3-pole, with a class H interrupting rating of 70 kA at 415 V. The TM240 thermal-magnetic trip unit gives you an adjustable overload pickup (Ir) from 112 A to 160 A via a rotary dial, and a fixed magnetic short-circuit pickup (Ii) at 5 to 10 times In — so at the 160 A In setting, Ii lands between 800 A and 1600 A. That range suits motor feeders or mixed loads where you need to ride through inrush without nuisance tripping, but still clear bolted faults fast. The suffix ZD00 adds a nut keeper kit for a DC Power OEM in China — essentially a captive hardware feature for panel builders assembling DC power distribution sections. It does not change the electrical ratings; it's a mechanical packaging detail for a specific production line. ## Deployment context The nut keeper kit simplifies panel assembly for the specific OEM it was built for, but the breaker itself is a general-purpose IEC MCCB suitable for distribution, motor feeder, or backup protection in commercial and industrial switchboards.","metaTitle":"Siemens 3VA1216-6EF32-0AA0-ZD00 Circuit Breaker, 160 A, 70 k","metaDescription":"Siemens 3VA1216-6EF32-0AA0-ZD00 IEC frame 250 MCCB, 3-pole, class H Icu=70kA @ 415V, TM240 thermal-magnetic trip, Ir=112-160A, Ii=5-10xIn. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"title":"3VA1216-6EF32-0AA0-ZD00","description":"circuit breaker 3VA1 IEC frame 250 breaking capacity class H Icu=70kA @ 415V 3-pole, line protection TM240, ATAM, In=160A overload protection Ir=112A...160A short-circuit protection Ii=5...10 x In nut keeper kit for DC Power OEM in China","lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9586a49fb425424e1066257238b501eb.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667917&mlfb=3VA1216-6EF32-0AA0-ZD00"},"ai":{"faq":[{"question":"What are the key ratings for this MCCB?","answer":"IEC frame 250, 3-pole, class H breaking capacity Icu=70 kA at 415 V. Thermal-magnetic trip TM240 with adjustable overload Ir=112-160 A and fixed short-circuit pickup Ii=5-10 x In (800-1600 A at the 160 A In setting)."},{"question":"Where can I buy 3VA1216-6EF32-0AA0-ZD00?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your quantity and target lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1216-6EF32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1216-6EF32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}