{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1220-5EF32-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1220-5EF32-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1220-5EF32-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1220-5EF32-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1220-5EF32-0AC0, molded case circuit breaker, 3-pole, TM240 overcurrent release, 200 A rated, interrupting 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, 17 kA at 690 V.","salesMarkdown":"At 40 °C it holds 200 A continuous without derating, and it only drops to 194 A at 55 °C and 176 A at 70 °C — so in a warm panel you still get nearly full rated current. Interrupting capacity is the headline: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V. ## Sizing and thermal performance The TM240 release is set for 200 A frame, but the actual trip curve depends on the thermal element — you get full 200 A up to 50 °C, then a gentle 3 % reduction per 5 °C step to 176 A at 70 °C. That thermal roll-off is standard for molded-case breakers; the 42 W maximum power loss gives a heat budget for enclosure ventilation planning. Dimensions: 105 mm wide, 158 mm high, 70 mm deep. That 70 mm depth keeps it within standard 200 mm deep enclosures — no need for a deeper gland plate. Comes with 2 auxiliary switches HQ factory-fitted, so you get status feedback without adding a separate accessory block.","metaTitle":"Siemens 3VA1220-5EF32-0AC0 SENTRON MCCB, 200 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA1220-5EF32-0AC0 molded case circuit breaker, 3-pole, 200 A rated, 187 kA interrupting at 240 V. TM240 release. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"105 mm","title":"3VA1220-5EF32-0AC0","Height":"158 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"30 kA","at 690 V":"17 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"194 A","at 60 °C":"188 A","at 65 °C":"182 A","at 70 °C":"176 A","Depth [In]":"2.76 in","Width [In]":"4.13 in","Height [In]":"6.22 in","description":"circuit breaker 3VA1 IEC frame 250 breaking capacity class M Icu=55kA @ 415V 3-pole, line protection TM240, ATAM, In=200A overload protection Ir=140A...200A short-circuit protection Ii=5...10 x In nut keeper kit 2 auxiliary switches HQ","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"42 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA12205EF320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/28d00bbbffb65e775de60d45fbfbdabe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=568551&mlfb=3VA1220-5EF32-0AC0"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA1220-5EF32-0AC0 at 415 V?","answer":"121 kA at 415 V. At 240 V it is 187 kA, at 440 V it is 75.6 kA, at 500 V it is 30 kA, and at 690 V it is 17 kA."},{"question":"Where can I buy 3VA1220-5EF32-0AC0?","answer":"This part is sourced and quoted to order through independent distribution. Availability and current pricing are confirmed at quote time against an RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1220-5EF32-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1220-5EF32-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}