{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1220-5EF32-0KE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1220-5EF32-0KE0","canonicalUrl":"https://aoctrl.com/siemens/3VA1220-5EF32-0KE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1220-5EF32-0KE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1220-5EF32-0KE0, molded case circuit breaker, 3-pole, 200 A rated current, 187 kA interrupting capacity at 240 V AC, line protection design.","salesMarkdown":"Its interrupting capacity reaches 187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V — meaning it can safely clear faults up to those levels without cascading upstream. Rated current holds at 200 A from 40 °C through 50 °C ambient, then derates to 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C. Maximum power loss is 42 W. For a panel builder, that means the breaker can be grouped in a 50 °C enclosure without current reduction — above that, the derating curve governs the actual load it can carry. It does not include an undervoltage release or ground-fault monitoring.","metaTitle":"Siemens 3VA1220-5EF32-0KE0 SENTRON MCCB, 200 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA1220-5EF32-0KE0 molded case circuit breaker, 200 A rated, 3-pole, 187 kA interrupting at 240 V. Current lifecycle. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"105 mm","Height":"158 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"30 kA","at 690 V":"17 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"194 A","at 60 °C":"188 A","at 65 °C":"182 A","at 70 °C":"176 A","Depth [In]":"2.76 in","Width [In]":"4.13 in","Height [In]":"6.22 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"42 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA12205EF320AA0","Design Of The Auxiliary Switch":"4 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1110618&mlfb=3VA1220-5EF32-0KE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1220-5EF32-0KE0/alternatives.json"},"ai":{"faq":[{"question":"What are the key interrupting ratings for 3VA1220-5EF32-0KE0?","answer":"187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V — these are the maximum fault currents the breaker can safely interrupt at each voltage level."},{"question":"Where can I buy 3VA1220-5EF32-0KE0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — no stock figures or price lists are published here."},{"question":"What is the rated current of 3VA1220-5EF32-0KE0 at different ambient temperatures?","answer":"200 A from 40 °C to 50 °C, then derated to 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1220-5EF32-0KE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1220-5EF32-0KE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}