{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1220-6EE32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1220-6EE32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1220-6EE32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1220-6EE32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VA1220-6EE32-0AA0, molded case circuit breaker, 3-pole, TM220 thermal-magnetic overcurrent release, 200 A at 40 °C, interrupting rating 220 kA at 240 V.","salesMarkdown":"Its job is to clear a fault before it propagates upstream, and the interrupting ratings back that: 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, 17 kA at 690 V. Rated continuous current is 200 A at 40 °C, and it holds that figure through 50 °C — only starts derating at 55 °C (194 A), dropping to 176 A at 70 °C. The TM220 designation on the overcurrent release means it's a thermal-magnetic trip unit fixed at 200 A — no interchangeable rating plugs, no electronic adjustment. For a sourcing decision, that locks the breaker to a 200 A feeder; if the BOM calls for a different amp rating, this isn't the variant. Dimensions are 105 mm wide, 158 mm high, 70 mm deep — a standard 3-pole MCCB footprint for a 200 A frame. No undervoltage release, no shunt trip, no communication function — this is a straight electromechanical breaker with a manual handle and a trip indicator (which is absent on this variant). If the spec calls for remote tripping or status feedback, you'd need a different 3VA option with the accessory slot populated.","metaTitle":"SENTRON 3VA1220-6EE32-0AA0 MCCB, 200 A, 3-Pole, TM220 Trip","metaDescription":"SENTRON 3VA1220-6EE32-0AA0 molded case circuit breaker, 200 A at 40 °C, 3-pole, TM220 thermal-magnetic trip, 220 kA at 240 V interrupting. Current lifecycle stage. Quoted to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"105 mm","title":"3VA1220-6EE32-0AA0","Height":"158 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"75.6 kA","at 500 V":"30 kA","at 690 V":"17 kA","at 40 °C":"200 A","at 45 °C":"200 A","at 50 °C":"200 A","at 55 °C":"194 A","at 60 °C":"188 A","at 65 °C":"182 A","at 70 °C":"176 A","Depth [In]":"2.76 in","Width [In]":"4.13 in","Height [In]":"6.22 in","description":"circuit breaker 3VA1 IEC frame 250 breaking capacity class H Icu=70kA @ 415V 3-pole, line protection TM220, ATFM, In=200A overload protection Ir=140A...200A short-circuit protection Ii=10 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"42 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM220","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2235c84b380c45bb39e344196dfa288e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=690391&mlfb=3VA1220-6EE32-0AA0"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1220-6EE32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1220-6EE32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}