{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1225-4EF32-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1225-4EF32-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1225-4EF32-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1225-4EF32-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1225-4EF32-0AH0, molded case circuit breaker, 3-pole, TM240 thermal-magnetic release, 250 A at 40 °C, 121 kA interrupting at 240 V.","salesMarkdown":"## SENTRON 3VA1225-4EF32-0AH0 — 250 A MCCB for Line Protection ## Interrupting Ratings Across Voltages The interrupting capacity varies with system voltage: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, 17 kA at 500 V, and 11.9 kA at 690 V. Above 50 °C, derating applies: 243 A at 55 °C, 237 A at 60 °C, 230 A at 65 °C, and 223 A at 70 °C. If the panel ambient exceeds 50 °C, the load must be reduced accordingly. ## Auxiliary Switching and Indication A trip indicator is present. The 105 mm width is a 3-pole frame size — verify busbar spacing and enclosure cutout against the existing panel layout. The supplied basic switch is order code 3VA12254EF320AA0.","metaTitle":"Siemens 3VA1225-4EF32-0AH0 SENTRON MCCB, 250 A, 3-Pole, TM24","metaDescription":"Siemens 3VA1225-4EF32-0AH0 SENTRON molded case circuit breaker, 250 A at 40 °C, 3-pole, TM240 release, 121 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"105 mm","title":"3VA1225-4EF32-0AH0","Height":"158 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"17 kA","at 690 V":"11.9 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"243 A","at 60 °C":"237 A","at 65 °C":"230 A","at 70 °C":"223 A","Depth [In]":"2.76 in","Width [In]":"4.13 in","Height [In]":"6.22 in","description":"circuit breaker 3VA1 IEC frame 250 breaking capacity class S Icu=36kA @ 415V 3-pole, line protection TM240, ATAM, In=250A overload protection Ir=175A...250A short-circuit protection Ii=5...10 x In nut keeper kit 2 auxiliary switches HQ 1 trip alarm switch HQ","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"57 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA12254EF320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1761642e7d8d2a634a944fb60101da85.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=568486&mlfb=3VA1225-4EF32-0AH0"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1225-4EF32-0AH0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is the interrupting capacity of 3VA1225-4EF32-0AH0 at 240 V?","answer":"121 kA at 240 V. At 415 V it is 75.6 kA, at 440 V it is 52.5 kA, at 500 V it is 17 kA, and at 690 V it is 11.9 kA."},{"question":"What type of release does 3VA1225-4EF32-0AH0 use?","answer":"A TM240 thermal-magnetic release, providing both overload and short-circuit protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1225-4EF32-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1225-4EF32-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}