{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1225-4GF42-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1225-4GF42-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1225-4GF42-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1225-4GF42-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1225-4GF42-0JH0, molded case circuit breaker, 250 A, 4-pole, line protection, 70 mm depth, 140 mm width, 158 mm height.","salesMarkdown":"## What the 250 A rating means for your panel That 250 A holds at 40 °C, 45 °C, and 50 °C without derating; at 55 °C it drops to 243 A, at 60 °C to 237 A, at 65 °C to 230 A, and at 70 °C to 223 A — so if your enclosure runs hot, the actual continuous current capacity is lower than the nameplate. The interrupting rating varies significantly with system voltage: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, 17 kA at 500 V, and 11.9 kA at 690 V. For a 480 V panel (common in North America), the relevant figure is the 440 V or 500 V value — 52.5 kA or 17 kA respectively — so verify your available fault current against the correct voltage column. ## Physical fit and auxiliary options This is a panel-mount MCCB, not a DIN-rail unit — plan for bolt-on busbar connections and a cutout in the mounting plate. A voltage trigger is present; undervoltage release is not included. The trip indicator is mechanical, visible on the front face.","metaTitle":"Siemens 3VA1225-4GF42-0JH0 SENTRON MCCB, 250 A, 4-Pole","metaDescription":"Siemens 3VA1225-4GF42-0JH0 SENTRON molded case circuit breaker, 250 A rated, 4-pole, line protection. Breaking capacity 121 kA at 240 V. Active production. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"140 mm","Height":"158 mm","Maximum":"250 A","Minimum":"250 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"17 kA","at 690 V":"11.9 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"243 A","at 60 °C":"237 A","at 65 °C":"230 A","at 70 °C":"223 A","Depth [In]":"2.76 in","Width [In]":"5.51 in","Height [In]":"6.22 in","Trip Indicator":"Yes","Number Of Poles":"4","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"57 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA12254GF420AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"100%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=568654&mlfb=3VA1225-4GF42-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1225-4GF42-0JH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1225-4GF42-0JH0?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What are the physical dimensions of 3VA1225-4GF42-0JH0?","answer":"70 mm deep, 140 mm wide, 158 mm high. This is a panel-mount footprint, not DIN-rail."},{"question":"Does this breaker include a shunt trip or undervoltage release?","answer":"It includes a shunt trip (STL) auxiliary release. An undervoltage release is not included with this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1225-4GF42-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1225-4GF42-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}