{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1225-5EF32-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1225-5EF32-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1225-5EF32-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1225-5EF32-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1225-5EF32-0CH0, molded case circuit breaker, 3-pole, 250 A, TM240 thermal-magnetic release, 187 kA at 240 V, line protection version with undervoltage release.","salesMarkdown":"## Line Protection MCCB with 187 kA Interrupting Capacity The line protection variant omits ground-fault sensing and communication, keeping it a straightforward, non-communicating breaker for standard overcurrent protection duty. ## Thermal Derating and Operating Envelope Above that, derating begins: 243.3 A at 55 °C, 236.5 A at 60 °C, 229 A at 65 °C, and 223 A at 70 °C (–). ## Integrated Undervoltage Release and Auxiliary Switching The trip indicator gives local visual confirmation of a fault trip. The 3-pole form factor fits standard SENTRON mounting bases; the 70 mm depth leaves clearance in shallow enclosures. Latching endurance is rated at 15,000 operations, which covers frequent switching in process control or machine-tool applications without early mechanical wear.","metaTitle":"Siemens SENTRON 3VA1225-5EF32-0CH0 MCCB, 250 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA1225-5EF32-0CH0 molded case circuit breaker, 250 A rated current, 187 kA breaking at 240 V, 3-pole, TM240 release, undervoltage release included. Active lifecycl","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"105 mm","title":"3VA1225-5EF32-0CH0","Height":"158 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"36 kA","at 690 V":"17 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"243.3 A","at 60 °C":"236.5 A","at 65 °C":"229 A","at 70 °C":"223 A","description":"circuit breaker 3VA1 IEC frame 250 breaking capacity class M Icu=55kA @ 415V 3-pole, line protection TM240, ATAM, In=250A overload protection Ir=175A...250A short-circuit protection Ii=5...10 x In nut keeper kit undervoltage release (UVR) 120-127V AC 50/60Hz 2 auxiliary switches HQ 1 trip alarm switch HQ","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"1 250 A","Adjustable response value current / lr min.":"175 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/364516f7314c4741d435a3bfb7cfd6da.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=568671&mlfb=3VA1225-5EF32-0CH0"},"ai":{"faq":[{"question":"What are the key ratings for 3VA1225-5EF32-0CH0?","answer":"Rated continuous current Iu is 250 A with a TM240 thermal-magnetic release. Interrupting capacity is 187 kA at 240 V, 121 kA at 415 V, 36 kA at 440 V, and 17 kA at 690 V (–). Rated insulation voltage Ui is 800 V."},{"question":"Does 3VA1225-5EF32-0CH0 include an undervoltage release?","answer":"Yes, it ships with a factory-installed undervoltage release (UVR). The auxiliary contact configuration is 2 auxiliary switches plus 1 trip alarm switch HQ."},{"question":"What is the closest functional second-source for 3VA1225-5EF32-0CH0?","answer":"The 3VA1112-5EF32-0CA0 is a peer within the same SENTRON 3VA family, but it carries a lower current rating and different breaking capacities. Drop-in compatibility depends on the specific panel layout and required interrupting rating — verify the frame size and mounting footprint against your existing cutout before substituting."},{"question":"Where can I buy 3VA1225-5EF32-0CH0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1225-5EF32-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1225-5EF32-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}