{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1225-5FF42-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1225-5FF42-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1225-5FF42-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1225-5FF42-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1225-5FF42-0HA0, molded case circuit breaker, 4-pole, 125 A rated, TM240 thermal-magnetic release, shunt trip (STL), line protection design, breaking capacity 187 kA at 240 V.","salesMarkdown":"Breaking capacity is voltage-dependent: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V. ## Thermal derating and power loss Above that, it derates linearly: 243 A at 55 °C, 237 A at 60 °C, 230 A at 65 °C, and 223 A at 70 °C. Maximum power loss is 57 W at rated current — relevant for enclosure heat calculations in a densely packed panel. ## Physical fit and integration The shunt trip release (STL) allows integration with emergency-stop circuits or undervoltage protection schemes — no separate undervoltage release is fitted on this variant.","metaTitle":"Siemens 3VA1225-5FF42-0HA0 SENTRON MCCB, 125 A, 4-Pole, Shun","metaDescription":"Siemens 3VA1225-5FF42-0HA0 SENTRON molded case circuit breaker, 125 A rated, 4-pole, TM240 release, shunt trip. Breaking capacity 187 kA at 240 V. Active production. Quoted on requ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"140 mm","Height":"158 mm","Maximum":"125 A","Minimum":"125 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"30 kA","at 690 V":"17 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"243 A","at 60 °C":"237 A","at 65 °C":"230 A","at 70 °C":"223 A","Depth [In]":"2.76 in","Width [In]":"5.51 in","Height [In]":"6.22 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"57 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA12255FF420AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"50%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=568727&mlfb=3VA1225-5FF42-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1225-5FF42-0HA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1225-5FF42-0HA0 at different voltages?","answer":"Breaking capacity is 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V."},{"question":"Where can I buy 3VA1225-5FF42-0HA0 and how is it quoted?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Siemens provide for 3VA1225-5FF42-0HA0?","answer":"As a SENTRON MCCB, it carries IEC 60947-2 certification and is designed to meet UL 489 requirements. RoHS and REACH declarations are standard from Siemens for this product line."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1225-5FF42-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1225-5FF42-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}