{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1225-5FF42-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1225-5FF42-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1225-5FF42-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1225-5FF42-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1225-5FF42-0HH0, molded case circuit breaker, 125 A, 4-pole, 187 kA interrupting at 240 V, line protection design, with shunt trip and auxiliary switches.","salesMarkdown":"## Part identity and what it does ## Breaking capacity across voltages Interrupting rating drops as voltage rises: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V. Derating starts above 50 °C: 243 A at 55 °C, 237 A at 60 °C, 230 A at 65 °C, 223 A at 70 °C. The 70 mm depth and 140 mm width mean it fits standard MCCB panel cutouts; the 158 mm height is typical for this frame size. ## Auxiliary and release configuration The shunt trip lets a remote PLC or E-stop circuit trip the breaker — common for emergency-off chains in conveyor or pump panels. Trip indicator and voltage trigger are present on the mechanism.","metaTitle":"Siemens 3VA1225-5FF42-0HH0 SENTRON MCCB, 125A, 4-Pole, 187kA","metaDescription":"Siemens 3VA1225-5FF42-0HH0 SENTRON molded case circuit breaker, 125 A, 4-pole, 187 kA at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"140 mm","Height":"158 mm","Maximum":"125 A","Minimum":"125 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"30 kA","at 690 V":"17 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"243 A","at 60 °C":"237 A","at 65 °C":"230 A","at 70 °C":"223 A","Depth [In]":"2.76 in","Width [In]":"5.51 in","Height [In]":"6.22 in","Trip Indicator":"Yes","Number Of Poles":"4","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"57 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA12255FF420AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"50%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=568729&mlfb=3VA1225-5FF42-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1225-5FF42-0HH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1225-5FF42-0HH0 and what is the lead time?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here, but a quote request gets you a firm answer."},{"question":"Will 3VA1225-5FF42-0HH0 drop into a panel specified around 3VA1110-5ED36-0AC0?","answer":"No — the 3VA1110-5ED36-0AC0 is a smaller frame (100 A, 3-pole) with different dimensions and a lower interrupting rating. The 3VA1225 is a 125 A, 4-pole frame with a 70 mm depth vs the 3VA1110's shallower profile. Panel cutouts and bus connections would need rework."},{"question":"What are the key ratings for this MCCB?","answer":"125 A continuous, 4-pole, 187 kA interrupting at 240 V, insulation voltage 800 V. Thermal derating starts above 50 °C. Shunt trip and two auxiliary switches plus trip alarm are included."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1225-5FF42-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1225-5FF42-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}