{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1225-6EF32-0BH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1225-6EF32-0BH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1225-6EF32-0BH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1225-6EF32-0BH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 250 circuit breaker, breaking capacity class H, Icu=70kA @ 415V, 3-pole, line protection TM240, ATAM, In=250A, overload protection Ir=175A...250A, short-circuit protection Ii=5...10 x In, with nut keeper kit, undervoltage release (UVR) 24V DC, 2 auxiliary switches HQ, 1 trip alarm switch HQ.","salesMarkdown":"The Siemens 3VA1225-6EF32-0BH0 is a 3-pole IEC frame 250 molded case circuit breaker from the 3VA1 series, rated for line protection with a TM240 thermal-magnetic trip unit. Breaking capacity class H delivers Icu=70kA at 415 V AC — enough to handle high-fault-current scenarios typical in industrial main feeders or large motor branch circuits without cascading upstream. The breaker includes a nut keeper kit for secure panel mounting, plus an undervoltage release (UVR) at 24 V DC for remote trip on loss of control voltage.","metaTitle":"Siemens 3VA1225-6EF32-0BH0 3VA1 IEC Frame 250 Breaker, 70kA","metaDescription":"Siemens 3VA1225-6EF32-0BH0 circuit breaker, 3VA1 IEC frame 250, breaking capacity class H Icu=70kA @ 415V, 3-pole, TM240, In=250A. Active lifecycle stage. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=568814&mlfb=3VA1225-6EF32-0BH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1225-6EF32-0BH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1225-6EF32-0BH0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA1225-6EF32-0BH0?","answer":"Breaking capacity class H: Icu=70kA at 415 V AC, 3-pole."},{"question":"What trip unit and protection settings does this breaker have?","answer":"TM240 thermal-magnetic trip unit with overload protection Ir adjustable 175 A to 250 A and short-circuit protection Ii adjustable 5 to 10 x In."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1225-6EF32-0BH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1225-6EF32-0BH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}