{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1225-6EF42-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1225-6EF42-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1225-6EF42-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1225-6EF42-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1225-6EF42-0JC0, molded case circuit breaker, 4-pole, 250 A at 40 °C, interrupting capacity 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V.","salesMarkdown":"It carries a continuous current rating of 250 A at 40 °C, derating to 223 A at 70 °C, which means the full 250 A is available in most standard panel environments — only above 55 °C does the rating start to drop. ## Interrupting capacity across voltage levels This 4-pole MCCB delivers 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V. ## Integrated accessories and footprint It measures 140 mm wide, 158 mm high, and 70 mm deep, which is the standard 4-pole SENTRON 3VA form factor.","metaTitle":"Siemens 3VA1225-6EF42-0JC0 SENTRON MCCB, 250 A, 4-Pole, 220","metaDescription":"Siemens SENTRON 3VA1225-6EF42-0JC0 molded case circuit breaker, 250 A rated at 40 °C, 4-pole, 220 kA at 240 V. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"140 mm","Height":"158 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"75.6 kA","at 500 V":"30 kA","at 690 V":"17 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"243 A","at 60 °C":"237 A","at 65 °C":"230 A","at 70 °C":"223 A","Depth [In]":"2.76 in","Width [In]":"5.51 in","Height [In]":"6.22 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"57 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA12256EF420AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"without","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=568851&mlfb=3VA1225-6EF42-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1225-6EF42-0JC0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA1225-6EF42-0JC0 and how is it quoted for volume purchases?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."},{"question":"What is 3VA1225-6EF42-0JC0's listed depth (70 mm) on this component line?","answer":"The listed depth is 70 mm, which matches the standard 4-pole SENTRON 3VA form factor — same depth as the 3-pole version."},{"question":"What is 3VA1225-6EF42-0JC0's listed width (140 mm) on this component line?","answer":"The listed width is 140 mm, standard for a 4-pole SENTRON 3VA MCCB."},{"question":"What compliance documentation does this brand provide for 3VA1225-6EF42-0JC0 (RoHS, REACH, UL, IEC)?","answer":"As a Siemens SENTRON product, this MCCB is designed to meet IEC 60947-2 and UL 489 standards. RoHS and REACH compliance documentation is available from Siemens upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1225-6EF42-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1225-6EF42-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}