{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1450-6EE32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1450-6EE32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1450-6EE32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1450-6EE32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1450-6EE32-0AA0, molded case circuit breaker, 3-pole, TM220 overcurrent release, rated 500 A at 40 °C, breaking capacity 220 kA at 240 V AC.","salesMarkdown":"The Siemens SENTRON 3VA1450-6EE32-0AA0 is a 3-pole molded case circuit breaker (MCCB) designed for line protection, carrying a continuous current rating of 500 A at 40 °C ambient and a rated insulation voltage of 800 V. Its TM220 thermal-magnetic release provides fixed overload and short-circuit protection, making it a straightforward fit for main feeder or large branch circuits in industrial distribution panels. At 240 V AC the interrupting rating reaches 220 kA, dropping to 154 kA at 415 V and 440 V, 121 kA at 500 V, and 17 kA at 690 V. That 220 kA figure at 240 V suits high-fault utility or transformer-fed services where available short-circuit current is extreme. The continuous current holds at 500 A through 50 °C ambient; above that it derates in 12 A steps per 5 °C increment, reaching 452 A at 70 °C. Panel builders should account for the 122.7 W maximum power loss when sizing enclosure ventilation. The 3-pole form factor and TM220 release mean no auxiliary electronics or communication module; it is a straight electromechanical device for line protection without ground-fault monitoring or undervoltage release.","metaTitle":"Siemens 3VA1450-6EE32-0AA0 SENTRON MCCB, 500 A, 3-Pole, TM22","metaDescription":"Siemens SENTRON 3VA1450-6EE32-0AA0 molded case circuit breaker, 500 A at 40 °C, 3-pole, TM220 release, 220 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","title":"3VA1450-6EE32-0AA0","Height":"248 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"154 kA","at 500 V":"121 kA","at 690 V":"17 kA","at 40 °C":"500 A","at 45 °C":"500 A","at 50 °C":"500 A","at 55 °C":"488 A","at 60 °C":"476 A","at 65 °C":"464 A","at 70 °C":"452 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","description":"circuit breaker 3VA1 IEC frame 630 breaking capacity class H Icu=70kA @ 415V 3-pole, line protection TM220, ATFM, In=500A overload protection Ir=350A...500A short-circuit protection Ii=10 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"122.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM220","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/95fe7799db73f2f5d895c88a6cde86d8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=690422&mlfb=3VA1450-6EE32-0AA0"},"ai":{"faq":[{"question":"Where can I buy 3VA1450-6EE32-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA1450-6EE32-0AA0 at 240 V?","answer":"The interrupting rating is 220 kA at 240 V AC, suitable for high-fault-current applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1450-6EE32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1450-6EE32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}