{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1510-5EF32-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1510-5EF32-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1510-5EF32-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1510-5EF32-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1510-5EF32-0KC0, molded case circuit breaker, 3-pole, 1000 A (40 °C), 187 kA at 240 V, line protection, shunt trip.","salesMarkdown":"## MCCB for high-fault line protection Rated insulation voltage 800 V, with breaking capacities that step down from 187 kA at 240 V to 121 kA at 415/440 V, then 75.6 kA at 500 V and 52.5 kA at 690 V. ## Current derating and thermal budget At 55 °C it derates to 960 A, at 60 °C to 940 A, at 65 °C to 920 A, and at 70 °C to 900 A. Maximum power loss is 330 W; the enclosure ventilation must clear that heat to avoid compounding the ambient rise. Dimensions: 320 mm height, 210 mm width, 120 mm depth. The 210 mm width is the three-pole frame — verify the mounting footprint against the existing backpanel cutout or DIN-rail adapter if retrofitting into an older SENTRON or 3VA panel. No communication function on this variant; it's a standalone thermal-magnetic or electronic-trip breaker with shunt trip control wiring only.","metaTitle":"Siemens 3VA1510-5EF32-0KC0 SENTRON MCCB, 1000 A, 3-Pole, 187","metaDescription":"Siemens 3VA1510-5EF32-0KC0 SENTRON molded case circuit breaker, 1000 A rated at 40 °C, 3-pole, 187 kA breaking at 240 V. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","Height":"320 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"52.5 kA","at 40 °C":"1 000 A","at 45 °C":"1 000 A","at 50 °C":"1 000 A","at 55 °C":"960 A","at 60 °C":"940 A","at 65 °C":"920 A","at 70 °C":"900 A","Depth [In]":"4.72 in","Width [In]":"8.27 in","Height [In]":"12.6 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"330 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA15105EF320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"750 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"10 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645680&mlfb=3VA1510-5EF32-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1510-5EF32-0KC0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3VA1510-5EF32-0KC0?","answer":"Rated 1000 A at 40 °C, 3-pole, with interrupting capacity of 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 52.5 kA at 690 V. Insulation voltage 800 V."},{"question":"Where can I buy 3VA1510-5EF32-0KC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Does 3VA1510-5EF32-0KC0 include a shunt trip?","answer":"Yes, the auxiliary release is a shunt trip (STL). It also includes two HQ auxiliary switches. No undervoltage release or ground-fault monitoring on this variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1510-5EF32-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1510-5EF32-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}