{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1580-5EF32-0HL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1580-5EF32-0HL0","canonicalUrl":"https://aoctrl.com/siemens/3VA1580-5EF32-0HL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1580-5EF32-0HL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1580-5EF32-0HL0, molded case circuit breaker, 3-pole, 800 A rated current at 40 °C, breaking capacity 121 kA at 415 V.","salesMarkdown":"The Siemens SENTRON 3VA1580-5EF32-0HL0 is a 3-pole molded case circuit breaker rated for 800 A continuous current at 40 °C, with a breaking capacity of 121 kA at 415 V. At 240 V the interrupting rating rises to 187 kA, and at 690 V it still holds 52.5 kA, so it handles high-fault-current service entrances and transformer secondaries without cascading. Above that it derates: 780 A at 55 °C, 761 A at 60 °C, 741 A at 65 °C, and 722 A at 70 °C. If your panel ambient runs toward 60 °C — common in tightly packed switchgear or near a furnace line — you lose about 5% of the headline rating. The maximum power loss is 240 W, so ventilation or spacing in the enclosure matters; a sealed cabinet with no airflow will push internal temperature above the free-air rating. ## Physical fit and auxiliary configuration A shunt trip release (STL) is installed for remote tripping.","metaTitle":"Siemens 3VA1580-5EF32-0HL0 SENTRON MCCB, 800 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA1580-5EF32-0HL0 molded case circuit breaker, 800 A at 40 °C, 3-pole, 121 kA breaking at 415 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"120 mm","Width":"210 mm","title":"3VA1580-5EF32-0HL0","Height":"320 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"52.5 kA","at 40 °C":"800 A","at 45 °C":"800 A","at 50 °C":"800 A","at 55 °C":"780 A","at 60 °C":"761 A","at 65 °C":"741 A","at 70 °C":"722 A","Depth [In]":"4.72 in","Width [In]":"8.27 in","Height [In]":"12.6 in","description":"circuit breaker 3VA1 IEC frame 1000 breaking capacity class M Icu=55kA @ 415V 3-pole, line protection TM240, ATAM, In=800A overload protection Ir=560A...800A short-circuit protection Ii=5 x In nut keeper kit shunt trip (STL) 12-30V DC, 24V AC 50/60Hz 2 auxiliary switches HQ 1 trip alarm switch HQ 1 electrical alarm switch","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"240 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA15805EF320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"750 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"10 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0ce7977805b8280afb8701b472881340.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=645575&mlfb=3VA1580-5EF32-0HL0"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1580-5EF32-0HL0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation at quote time."},{"question":"What are the key ratings of 3VA1580-5EF32-0HL0?","answer":"It is a 3-pole molded case circuit breaker rated 800 A at 40 °C with a breaking capacity of 121 kA at 415 V and 187 kA at 240 V. Dimensions are 320 x 210 x 120 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1580-5EF32-0HL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1580-5EF32-0HL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}