{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series molded case circuit breaker, 3VA2010-5HL32-0AA0, 3-pole, 100 A rated current, ETU320 electronic trip unit, line protection design.","salesMarkdown":"## What the ratings mean for your panel The Siemens SENTRON 3VA2010-5HL32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current with no derating across the full ambient range from 40 °C to 70 °C — that's a flat thermal curve, so you don't lose headroom when the panel runs hot. Breaking capacity hits 187 kA at 240 V, 121 kA at 415 V, and still holds 75.6 kA at 500 V — numbers that put this in the high-fault tier for industrial distribution. At 690 V it drops to 3 kA, so know your system voltage before you commit. The ETU320 electronic trip unit gives you adjustable overload and short-circuit protection curves — it's a line-protection design, not a motor-protection device, so spec it for feeder or main breaker duty. ## Panel fit and mounting Dimensions: 105 mm wide, 181 mm tall, 86 mm deep. Mounts on a DIN rail or direct panel-mount via the screw terminals. The front face carries IP40 protection — fine for a dry indoor enclosure, not for washdown zones. No undervoltage release, no shunt trip, no communication module on this variant — it's a straight breaker with the ETU320. If you need remote tripping or status feedback, you'll add external accessories.","metaTitle":"Siemens 3VA2010-5HL32-0AA0 SENTRON MCCB, 100 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2010-5HL32-0AA0 molded case circuit breaker, 100 A continuous, 3-pole, ETU320 release. Breaking capacity 187 kA at 240 V. Current lifecycle. Quoted to order agai","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0a6e41b2555654454e966a8200c15ac7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=182897&mlfb=3VA2010-5HL32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2010-5HL32-0AA0?","answer":"Submit an RFQ through this listing. Pricing and stock levels are confirmed at quote time through independent distribution — no automated figures are published here."},{"question":"What is the closest functional second-source to 3VA2010-5HL32-0AA0?","answer":"The 3VA1110-5ED32-0AA0 is a functional peer in the same SENTRON family, but it uses a different trip unit and may have different breaking capacity ratings. Verify the trip curve and SCCR against your coordination study before substituting."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"The SENTRON 3VA2 series carries IEC 60947-2 certification. RoHS and REACH declarations are standard from Siemens; request them with your order for your compliance file."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}