{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL32-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL32-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2, molded case circuit breaker, 3-pole, 100 A continuous, 187 kA at 240 V, line protection, 2 auxiliary switches HP, no trip indicator.","salesMarkdown":"The Siemens 3VA2010-5HL32-0AB0 is a SENTRON 3VA2 molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. The breaking capacity is the headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. That 86 mm depth is the can depth behind the panel — check your gland plate clearance if you're retrofitting into a shallow enclosure. No communication function means no Modbus or PROFIBUS gateway inside — if you need remote trip indication, the 2 auxiliary switches HP are your only signal path.","metaTitle":"3VA2010-5HL32-0AB0 SENTRON MCCB, 100 A, 187 kA at 240 V","metaDescription":"Siemens 3VA2010-5HL32-0AB0 SENTRON molded case circuit breaker, 3-pole, 100 A continuous, 187 kA breaking at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20105HL320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HP","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=321413&mlfb=3VA2010-5HL32-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0AB0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-5HL32-0AB0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is the breaking capacity of 3VA2010-5HL32-0AB0 at different voltages?","answer":"187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. The 187 kA at 240 V is the highest rating — suitable for high-fault-current main distribution panels."},{"question":"Does 3VA2010-5HL32-0AB0 have a trip indicator or communication?","answer":"No trip indicator and no communication function. It has 2 auxiliary switches HP for remote status indication. No undervoltage release or ground-fault monitoring is included."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL32-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}