{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL32-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL32-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5HL32-0AC0, 3-pole molded case circuit breaker, 100 A, line protection, ETU320 release, 187 kA at 240 V.","salesMarkdown":"The 100 A continuous rating holds flat from 40 °C to 50 °C; above that it derates in 3.75 A steps per 5 °C, down to 85 A at 70 °C (–). The ETU320 release is a basic electronic trip with fixed settings — no communication, no voltage trigger, no ground-fault monitoring. It's a straightforward line-protection device: set it, torque it, and it runs. The 2 auxiliary switches HQ give you status feedback for the PLC or remote indication. The 3VA2010-5HL32-0AC0 measures 105 mm wide by 181 mm tall by 86 mm deep — a standard SENTRON 3VA frame size that drops into a DIN-rail or screw-mount panel.","metaTitle":"Siemens SENTRON 3VA2010-5HL32-0AC0 MCCB, 100A, 187kA at 240V","metaDescription":"Siemens SENTRON 3VA2010-5HL32-0AC0 molded case circuit breaker, 3-pole, 100A rated, 187kA interrupting at 240V. Active production, sourced to order. RFQ for current pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"3.4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-5HL32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=155104&mlfb=3VA2010-5HL32-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0AC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-5HL32-0AC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting rating of 3VA2010-5HL32-0AC0 at 240 V?","answer":"187 kA at 240 V — high enough for main distribution board duty with full selectivity."},{"question":"Will 3VA2010-5HL32-0AC0 drop into a panel specified around 3VA2010-5HL36-0BE0?","answer":"Both are 3-pole SENTRON 3VA frame MCCBs with the same 100 A continuous rating and identical dimensions (105 x 181 x 86 mm). The difference is the trip unit: this one carries an ETU320, while the -5HL36-0BE0 uses a different ETU variant. If the panel's trip curve and auxiliary contact count match, it will swap in without rewiring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL32-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}