{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL32-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL32-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5HL32-0BA0, molded case circuit breaker, 3-pole, 100 A rated continuous current, line protection design, with undervoltage release, 187 kA breaking capacity at 240 V.","salesMarkdown":"It carries a 187 kA breaking capacity at 240 V, dropping to 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V — the SCCR headroom you need for high-fault service-entrance or feeder positions. ## Undervoltage release and trip behavior No trip indicator and no voltage-trigger auxiliary, so if you need remote status feedback, plan for an external auxiliary switch block. The UVR coil draw and dropout voltage aren't in this spec set, but typical SENTRON UVRs hold at 0.7–0.85 x rated control voltage; verify against your control transformer sizing. ## Thermal performance and panel fit That's a 4.13 x 7.13 x 3.39 inch footprint — fits standard SENTRON 3VA mounting patterns; no rewiring if swapping into a panel originally built for a 3VA1110-series frame of similar ampacity.","metaTitle":"Siemens 3VA2010-5HL32-0BA0 SENTRON MCCB, 100 A, 3-Pole, UVR","metaDescription":"Siemens SENTRON 3VA2010-5HL32-0BA0 molded case circuit breaker, 100 A continuous, 3-pole, 187 kA at 240 V. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20105HL320AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=269100&mlfb=3VA2010-5HL32-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0BA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-5HL32-0BA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) for current availability and pricing — no stock or price figures are published here."},{"question":"Will 3VA2010-5HL32-0BA0 drop into a panel specified around 3VA1110-5EF32-0LA0 without rewiring?","answer":"Both are SENTRON 3VA frame breakers with the same 3-pole footprint and mounting pattern, so mechanical fit is the same. The 3VA2010 variant carries an undervoltage release that the 3VA1110 may not; if the panel wiring already includes UVR control voltage, it drops in. If not, the UVR coil must be powered or the breaker won't latch — check the control schematic before swapping."},{"question":"What is the continuous current rating of this MCCB?","answer":"Rated 100 A continuous, and it holds that rating from 40 °C through 70 °C ambient (–) with no derating required."},{"question":"What compliance documentation does this brand provide for 3VA2010-5HL32-0BA0?","answer":"As a Siemens SENTRON MCCB, it carries CE marking for the European market and is designed to IEC 60947-2. UL/CSA listings are typical for the 3VA series but are not confirmed in this spec set; verify with the manufacturer's declaration or request the compliance pack with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL32-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}