{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL32-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL32-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5HL32-0DA0, 3-pole molded case circuit breaker, line protection, rated 100 A continuous, 187 kA interrupting at 240 V AC, with undervoltage release.","salesMarkdown":"## MCCB for high-fault panels Its 100 A continuous rating (Iu) holds at ambient temperatures up to 50 °C without derating; at 55 °C it still carries 96.25 A, and at 70 °C it delivers 85 A — useful for panels with elevated internal heat. At 415/440 V it still breaks 121 kA, and at 690 V it drops to 3.4 kA — so for 690 V systems, verify the available fault current stays under that threshold. The overcurrent release is an ETU320 electronic trip unit, which provides adjustable long-time, short-time, and instantaneous protection curves. No auxiliary contacts, ground-fault monitoring, or communication function are built in; those would need separate add-on modules. Panel builders should verify the depth clearance for the undervoltage release wiring and any rear-connection terminals.","metaTitle":"Siemens 3VA2010-5HL32-0DA0 SENTRON MCCB, 100A, 187kA at 240V","metaDescription":"Siemens SENTRON 3VA2010-5HL32-0DA0 molded case circuit breaker, 3-pole, 100A, 187kA at 240V AC. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"3.4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"16 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-5HL32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=439100&mlfb=3VA2010-5HL32-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0DA0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA2010-5HL32-0DA0 and how is it quoted for volume purchases?","answer":"This part is supplied through independent distribution channels. It is quoted to order against an RFQ; availability and pricing are confirmed at the time of quote. Volume pricing and scheduled deliveries are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL32-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}