{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL32-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL32-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5HL32-0DC0, molded case circuit breaker, 3-pole, 100 A continuous rating, 187 kA breaking capacity at 240 V AC, line protection design with undervoltage release and 2 auxiliary switches HQ.","salesMarkdown":"The adjustable thermal-magnetic trip range spans 150 A minimum to 1 200 A maximum, so the same frame covers a wide band of settings; you set the actual pickup to match the load. At 240 V it clears 187 kA — that's utility-grade fault current, typical for a service entrance or a transformer secondary. At 415 V and 440 V it still handles 121 kA, and at 500 V it's 75.6 kA. ## Built-in auxiliaries and release — what's in the can The UVR means the breaker trips if control voltage drops — standard for emergency-stop circuits or undervoltage protection on motor feeders. The two aux switches give you status feedback (open/closed) to a PLC or a panel lamp without adding external limit switches. Mounts on a standard DIN rail or direct panel; the 105 mm width (4.13 in) and 86 mm depth (3.39 in) mean it fits a standard distribution board cutout.","metaTitle":"Siemens 3VA2010-5HL32-0DC0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2010-5HL32-0DC0 molded case circuit breaker, 100 A continuous, 3-pole, 187 kA breaking at 240 V. Current production. Available to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20105HL320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=141433&mlfb=3VA2010-5HL32-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0DC0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2010-5HL32-0DC0's listed depth?","answer":"Depth is 86 mm (3.39 in). Width is 105 mm (4.13 in), height is 181 mm (7.13 in)."},{"question":"Will 3VA2010-5HL32-0DC0 drop into a panel specified around 3VA1110-5ED36-0AC0 without rewiring?","answer":"The 3VA2010 shares the same 105 mm width and DIN-rail footprint as the 3VA1110 frame, so it fits the same panel cutout. However, the 3VA2010 includes a factory-installed undervoltage release that requires a separate control circuit — the wiring diagram differs from a bare 3VA1110. If the original panel had no UVR wiring, you'll need to add it."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL32-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}