{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL32-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL32-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5HL32-0JA0, 3-pole molded case circuit breaker, 100 A rated continuous current, 187 kA interrupting capacity at 240 V, ETU320 overcurrent release, shunt trip.","salesMarkdown":"The Siemens SENTRON 3VA2010-5HL32-0JA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying 100 A continuous current (Iu) at 40 °C and delivering 187 kA interrupting capacity at 240 V — enough to handle high-fault utility feeds or large transformer secondaries without cascading upstream. It ships with an ETU320 electronic overcurrent release and a factory-integrated shunt trip (STL) for remote emergency-off or undervoltage tripping, so it pulls double duty as both a feeder breaker and a safety disconnect in one footprint. At 415 V and 440 V it still holds 121 kA, and at 500 V it drops to 79 kA. The 690 V rating of 3.4 kA is low, so if your line runs at 690 V phase-to-phase, this is not the right breaker for that bus. Above 55 °C it steps down: 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. If the breaker lives near a hot drive cabinet or a steam line, plan for that curve. The 3VA2010-5HL32-0JA0 measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard 3-pole MCCB footprint that bolts directly onto a DIN rail or a mounting plate. Maximum power loss is 13.5 W — negligible for panel heat budgeting, but worth noting if you're packing a dozen of these in a sealed cabinet.","metaTitle":"Siemens 3VA2010-5HL32-0JA0 SENTRON MCCB, 100A, 187kA at 240V","metaDescription":"Siemens SENTRON 3VA2010-5HL32-0JA0 molded case circuit breaker, 3-pole, 100A rated, 187kA interrupting at 240V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"3.4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-5HL32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=381616&mlfb=3VA2010-5HL32-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-5HL32-0JA0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Contact us with your quantity and target delivery window; we confirm availability and current pricing at quote time."},{"question":"Will 3VA2010-5HL32-0JA0 drop into a panel specified around 3VA1010-2ED32-0JA0?","answer":"Both are 3-pole SENTRON MCCBs in the same physical frame size (105 mm wide, 181 mm tall, 86 mm deep), so the mechanical footprint and bus-bar spacing are identical. The key difference is the overcurrent release: the 3VA2010-5HL32-0JA0 carries an ETU320 electronic trip unit, while the 3VA1010-2ED32-0JA0 uses a different release design. Verify the trip curve and auxiliary wiring before swapping — the shunt trip and auxiliary contact arrangements may differ."},{"question":"What are the key ratings for 3VA2010-5HL32-0JA0?","answer":"Rated continuous current Iu is 100 A. Interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 3.4 kA at 690 V. Rated insulation voltage is 800 V. Operating temperature range is -25 °C to +70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL32-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}