{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5HL32-0JH0, molded case circuit breaker, 3-pole, 100 A continuous, line protection design, breaking capacity 187 kA at 240 V.","salesMarkdown":"## Siemens SENTRON 3VA2010-5HL32-0JH0 — 100 A MCCB for Line Protection It carries a maximum breaking capacity of 187 kA at 240 V AC, stepping down to 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V — the voltage-dependent curve that governs fault clearing in your system. Power loss is 13.5 W maximum at rated current — a figure to account for in enclosed panel thermal calculations, especially when grouping multiple breakers. ## Auxiliary and Release Configuration The trip indicator and voltage trigger are present; undervoltage release is not included on this order code. No ground-fault monitoring or communication function is fitted. The depth of 86 mm (3.39 in) fits most shallow enclosures; verify clearance for the shunt trip wiring and auxiliary switch connections.","metaTitle":"Siemens 3VA2010-5HL32-0JH0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2010-5HL32-0JH0 molded case circuit breaker, 100 A continuous, 3-pole, line protection. Breaking capacity 187 kA at 240 V. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA20105HL320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=14389&mlfb=3VA2010-5HL32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for 3VA2010-5HL32-0JH0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time; the part is sourced through independent distribution channels."},{"question":"Will 3VA2010-5HL32-0JH0 drop into a panel specified for 3VA1020-2ED32-0DD0?","answer":"Both are 3-pole SENTRON MCCBs, but the 3VA1020-2ED32-0DD0 is a different variant with different auxiliaries and release configuration. Check the physical dimensions — the 3VA2010-5HL32-0JH0 measures 181 x 105 x 86 mm — and verify that the shunt trip wiring and auxiliary switch count match your panel design before substituting."},{"question":"What is the breaking capacity of this MCCB at 415 V?","answer":"121 kA at 415 V AC, the same rating as at 440 V. At 240 V it reaches 187 kA, and at 690 V it drops to 3 kA."},{"question":"Does this breaker require derating at high ambient temperatures?","answer":"No — the 100 A continuous rating holds from 40 °C through 70 °C without derating. The maximum operating temperature is 70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}