{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2010-5HL32-0JL0, molded case circuit breaker, 3-pole, 100 A, line protection, ETU320 electronic trip unit, 187 kA at 240 V, 121 kA at 415 V.","salesMarkdown":"The Siemens 3VA2010-5HL32-0JL0 is a SENTRON molded case circuit breaker rated for 100 A continuous current at 40 °C, with a 3-pole configuration and an ETU320 electronic trip unit for line protection. Its interrupting capacity hits 187 kA at 240 V and 121 kA at both 415 V and 440 V, dropping to 79 kA at 500 V and 3.4 kA at 690 V — so it handles high-fault service-entrance or distribution panels where the available fault current is substantial at lower voltages. The 800 V rated insulation voltage (Ui) means it's rated for 480/600 V class systems without derating the insulation. This breaker includes a shunt trip (STL) auxiliary release and an auxiliary contact block with 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ version). At 40 °C, 45 °C, and 50 °C the breaker holds its full 100 A rating. At 55 °C it derates to 96.25 A, at 60 °C to 92.5 A, at 65 °C to 88.75 A, and at 70 °C to 85 A. If your panel ambient runs above 50 °C, you need to account for that 1.5 A per degree drop above 50 °C. The maximum operating temperature is 70 °C; storage range is -40 °C to 80 °C. Dimensions are 105 mm wide, 181 mm high, and 86 mm deep — a standard 3-pole MCCB footprint that fits most SENTRON panelboards and distribution boards.","metaTitle":"Siemens 3VA2010-5HL32-0JL0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2010-5HL32-0JL0 molded case circuit breaker, 100 A, 3-pole, line protection, ETU320 release, 187 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"3.4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-5HL32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=338831&mlfb=3VA2010-5HL32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL32-0JL0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA2010-5HL32-0JL0 drop into a panel specified for 3VA1110-5EE32-0JA0?","answer":"No. The 3VA2010 uses a larger frame (3VA2) than the 3VA1 series. The mounting hole pattern and bus-bar connections differ, so it won't physically interchange without panel rework."},{"question":"What compliance documentation is available for this MCCB?","answer":"As a Siemens SENTRON product, it carries UL, CSA, and IEC certifications standard for the series. RoHS and REACH compliance declarations are available from Siemens documentation. Specific certificate numbers are not listed in this record."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}