{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2010-5HL36-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2010-5HL36-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3-pole, 100 A, 187 kA at 240 V, ETU320 electronic trip unit, IP40 front, 86 mm depth.","salesMarkdown":"## Line protection MCCB with ETU320 — 100 A, 187 kA SCCR The front face is IP40-rated — suitable for enclosure mounting behind a panel door, not for washdown exposure. Mechanical endurance is rated at 20,000 cycles.","metaTitle":"Siemens 3VA2010-5HL36-0AB0 SENTRON MCCB, 100A, 187kA at 240V","metaDescription":"Siemens 3VA2010-5HL36-0AB0 SENTRON molded case circuit breaker, 100A rated continuous current, 187kA interrupting at 240V, ETU320. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"3.4 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"13.5 W","Auxiliary contact version":"2 auxiliary switches HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2010-5HL36-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=473789&mlfb=3VA2010-5HL36-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2010-5HL36-0AB0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2010-5HL36-0AB0 and get a price?","answer":"This part is available to order through independent distribution. Submit an RFQ for current availability and pricing — stock and lead time are confirmed at quote time."},{"question":"What are the key ratings of 3VA2010-5HL36-0AB0?","answer":"Rated continuous current Iu is 100 A, interrupting capacity is 187 kA at 240 V (121 kA at 415/440 V, 79 kA at 500 V, 3.4 kA at 690 V). It is a 3-pole molded case circuit breaker with ETU320 electronic trip unit, 800 V rated insulation voltage, and IP40 front protection."},{"question":"Does 3VA2010-5HL36-0AB0 include a trip indicator or undervoltage release?","answer":"No. This variant has no trip indicator, no undervoltage release, no communication function, no phase-failure detection, no ground-fault monitoring, and no auxiliary release. It ships with two HP auxiliary switches only."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2010-5HL36-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2010-5HL36-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}